© 2019 Baker Hughes, a GE company, LLC. All rights reserved.
48 |
=
BHGE
Auto Tune
Auto Tune normally takes three to ten minutes and strokes the valve in large and small steps to
set the PID positioning parameters for best response to an input signal change.
This procedure overrides any previous configuration done using presets.
To auto tune the SVi1000:
1. Set the
Configuration Selector Switch
to the auto tuning parameter
0
for an ATO valve (Air to Open application)
8
for an ATC valve (Air to Close application).
Figure 24
Configuration Selection Switch
2. Press the
Autotune
button until green LED 3 lights, then release (
approximately 2
to 7 seconds
). The unit goes into a Commission Process and green LED 3 blinks.
The autotune process occurs.
When the autotune process is complete the unit automatically returns to Normal
mode.
Press
Cancel
to abort the process and the green LED 3 goes off, the device returns
to Normal mode and no changes to the tuning parameters occur.
Configuration
Switch
Autotune
Button
and
LED 3
Cancel
Button
and LED 4
Selection
Содержание BAKER HUGHES Masoneilan SVi 1000
Страница 1: ...Masoneilan SVi 1000 Positioner Quick Start Guide Rev L BHGE Data Classification Public...
Страница 8: ...This page intentionally left blank...
Страница 18: ...This page intentionally left blank...
Страница 38: ...This page intentionally left blank...
Страница 56: ...This page intentionally left blank...
Страница 86: ...This page intentionally left blank...
Страница 87: ......