FP400 Series Installation Manual
7
2 I
NSTALLATION GUIDE
This product has been developed in compliance with the EN54-2 and UN54-4 (UNE
23007) standard and have approvals pending. It must be installed by qualified personnel,
taking into account the EN54-14 (UNE 23007-14) standard as well as the corresponding
local authority’s laws.
2.1 Installation
Remove the front cover from the panel before installation.
The panel must be installed in a clean, dry place free from vibrations with a temperature
between 5º and 40º C. The relative humidity must not exceed 95%. There should be no
condensation. The panel should be installed where the risk of fire is minimal and the
place is protected by the fire detection system. Risk of mechanical damage must be
avoided.
2.1.1 Fixing the panel to the wall
Fix the panel to the wall at an approximate height of 1.5 metres from the floor, in a place
with easy access. The Panel LED indicators should be at eye-level.
Create the cable holes you require in the panel before fixing it to the wall. Do
not perforate the panel in places other than those indicated. Avoid dropping
shavings or pieces of removed casing inside the panel as this may damage
the electronic circuits. PG11-type cable adapters may be used.
2.1.2 Selecting a language
The panel is designed for simple language selection and configuration.
Take the language sheet provided, select the appropriate language and cut out the
inserts along the pre-cut lines. Slide each insert into the relevant slot on the front of the
panel. See Figure 4 Insertion of language inserts.
The language sheet contains blank inserts for configuring additional
languages.
Figure 4: Insertion of language inserts