16
FP400 Series Installation Manual
Figure 21: Active EOL configuration
Active EOL active
Active EOL inactive
Figure 22: Connection of a diode in an active end-of-line installation
The active end-of-line module is optional.
2.3.3 Configuration for remote reseting
You may activate
either
active end-of-line resistors or remote reset mode.
You may not activate both simultaneously.
Remote Reset mode
changes the normal function of the class change input. If the class
change input is activated, then the reset will be activated. If the class change input
remains activated a fault is shown activating the fault relay.
Use DIP switch 8 to activate this mode (see Figure 23 Remote reset configuration).
Figure 23: Remote reset configuration
Remote reset active
Remote reset inactive
2.4 Master modules
Two versions of the master module are available: a master module with 24 VDC outputs
and a master module with potential free relay outputs.
Refer to individual module installation guides for complete product features
and installation details.