FP400 Series Installation Manual
23
Calculating battery life in standby time
bc = battery capacity (FP402, FP404) = 2.6 A/h x 80% = 2.08 Ah
bc = battery capacity (FP408, FP412, FP416) = 7 A/h x 80% = 5.6 Ah
pa = panel current in mains fault (including all EOL resistors) (mA)
pc = panel current in alarm in 1 zone (including all EOL resistors) (mA)
yy = detector current (refer to detector instruction manual) (uA)
zz = number of detectors in installation
aux = auxiliary current (mA)
Sounder = sounder current (refer to sounder instruction manual) (mA)
Table 1: Panel current in mains fault and alarm (1 zone)
pa
pc
FP402 75
115
FP404 80
130
FP408 110
145
FP412 115
160
FP416 135
180
Example calculation (using FP408)
Zone 1: 15 optical detectors
Zone 2: 10 manual call points
Zone 3: 5 heat detectors
Use 50 mA on auxillary
Use 300 mA on sounders
Total current for detectors (de):
(zz x yy)
------------ = de
1000
de (zone 1) = 15 x 100/1000 = 1.5 mA
de (zone 2) = 0 (manual call point has no current in standby)
de (zone 3) = 5 x 100/1000 = 0.5 mA
de = 1.5 + 0 + 0.5 = 2 mA
Standby current (sc):
pa + de + aux = sc
pa (FP408) = 110
110 + 2 + 50 = 162
Current with 1 zone in alarm (zc):
Содержание ARITECH FP400 Series
Страница 25: ...FP400 Series Installation Manual 25 ...
Страница 26: ...26 FP400 Series Installation Manual ...
Страница 27: ...FP400 Series Installation Manual 27 ...
Страница 28: ... 1050086 ...