Type AKRU Breakers
The fused low voltage power
drouHbffia�r mee�NEMA
standard SG3 and ANSI
C37.13, and C37.28. They
provide protection for sys
tems with available fault
current to
200,000
Amperes
RMS symmetrical. Current
limiting fuses are provided
as an integral part of the
fused draw out breakers in
the
800
and
1600
Ampere
frame sizes. The
3200
and
4000
Ampere frames are
available with coordinated
fuses separately mounted in
a draw out fuse carriage or
fuse roll out element (station-
Open Fuse Lock Out Indicators
8
ary mounted fused breakers
are not available.)
An open fuse lock out
device is an integral part of
all fused power circuit break
ers. This device prevents
single phasing by monitoring
the fuses. Should any fuse
blow, this direct acting
device trips the breaker,
opening all three poles
simultaneously. Individual
phase indicators pin point
the blown fuse. The breaker
remains locked out until the
fuse is replaced and the
device is reset.
AKRU-50 Fuses