Trip Devices
EC Trip Devices
DC Applications
General
Type EC overcurrent trip
devices are magnetically
operated, using a series coil
(or single conductor and an
associated magnetic struc
ture) to provide tripping
force. Three basic character
istics: long-time delay, short
time delay and i nstantane
ous, can be used in various
combinations to suit the
application.
Type
EC-2A
Long-Time Delayis
accomplished with a
positive-displacement oil
piston. Sealing of the assem
bly eliminates variations
caused by atmospheric con
tamination, and silicone oil
minimizes variations in time
delay due to changes in
ambient temperature.
Short-Time Delay is
accomplished with a rugged
mechanical escapement.
lnstantaneoustripping
is obtained when a tension
spring yields to the force
exerted on the magnetic
armature at short circuit
current levels, permitting the
armature to move indepen
dently of the time delay pis
ton.
AKR breakers with EC
trips are for use on DC sys
tem voltages, and are avail
able in ratings of 40-6000
amperes. One EC trip device
Type
EC-1
is mounted in each breaker
pole and contains functional
adjustments, overcurrent
detection and tripping hard
ware.
EC trip devices are availa
ble as type EC-2A (standard
for frames through 2000A),
EC-1 (optional for frames
through 2000A) and EC-18
(standard for 4000 and
6000A frames). Trip charac
teristics are described in the
table below.
Type
EC-18
Trip Device for
600-2000
amp frame breakers.
Available in combinations of long-time and
instantaneous elements, or instantaneous
alone.
Trip Device for
600-2000
amp frame breakers.
Combines long-time and short-time elements
for intentional delay up to the short-time rating
of the breaker. Instantaneous may be added.
Trip Device for
4000
and
6000
amp frame
breakers. Combines long-time and short-time
elements for intentional delay up to the short
time rating of the breaker. Instantaneous may
be added.
Table
22.1
Adjustment Ranges
for EC
Trip Devices
Trip
Long-Time
Short-Time
Instantaneous
Device
Pickup
<D
Delay®
Pickup
Delay®
Pickup
(1A) MAX- adj 15-38 sec
or
4-9X
EC-2A 80-160%X
(1B) INTER- adj 7.5-18 sec
-
-
6-12X
(±10%)
or
9-15X or
(1C) MIN -adj 33-82 sec
80-250% X
®
(1A) MAX- 30sec
(2A)
MAX - 23 sec
or
2-5X
or
High Set
EC-1
80-160%X
(1B) INTER -15 sec
3-7X or
(2B) INTER -15 sec
up to 15X
(±10%)
or
4-10X
or
Non-Adjustable
(1C) MIN- 5 sec
(2C) MIN -07 sec
(2AA) MAX -20 sec
(188) MAX-45 sec
2-5X
or
4-9X
EC-18 80-160%X
or
3-7Xor
(288) INTER- 13 sec
6-12X
(±15%)
(1CC) MIN- 2 sec
4-10X
or
9-15X or
(2CC) MIN - 07 sec
80-250% X
®
<D
X
=
Trip device ampere rating. If trip devices are set above 100% for coordination purposes, such settings do not
increase the breaker's continuous current rating.
®
At lower limit of band at 6 times pickup setting.
®
At lower limit of band at 2V2 times pickup setting.
®
Low-set instantaneous. Not available in combination with long time delay.
22