AN-15 Terminal 53 High Ref./Feedb. Value
Range:
Function:
.
AN-16 Terminal 53 Filter Time Constant
Range:
Function:
0.001 s
*
[0.001 - 10
s]
NOTE
This parameter cannot be adjusted
while the motor is running.
Enter the time constant. This is a first-
order digital low pass filter time constant
for suppressing electrical noise in terminal
53. A high time constant value improves
dampening but also increases the time
delay through the filter.
3.8.3 AN-2# Analog Input 54
Parameters to configure the scaling and limits for Analog
Input 2 (terminal 54)
AN-20 Terminal 54 Low Voltage
Range:
Function:
0.07 V
*
[-10.00 - par.
AN-21 V]
Enter the low voltage value. This
analog input scaling value should
correspond to the minimum reference
See also .
AN-21 Terminal 54 High Voltage
Range:
Function:
10 V
*
[par. AN-20 -
10 V]
Enter the high voltage value. This analog
input scaling value should correspond to
the high reference/feedback value set in
AN-25 Terminal 54 High Ref./Feedb. Value
.
AN-22 Terminal 54 Low Current
Range:
Function:
0.14
mA
*
[0 - par.
AN-23 mA]
Enter the low current value. This
reference signal should correspond to the
minimum reference value, set in
. The value must
be set at >2 mA in order to activate the
Live Zero Time-out Function in
AN-23 Terminal 54 High Current
Range:
Function:
20 mA
*
[par. AN-22 -
20 mA]
Enter the high current value
corresponding to the high reference/
feedback value set in
AN-25 Terminal
54 High Ref./Feedb. Value
.
AN-24 Terminal 54 Low Ref./Feedb. Value
Range:
Function:
0 ReferenceFeed-
backUnit
*
[-999999.999 -
999999.999
ReferenceFeed-
backUnit]
Enter the analog
input scaling value
that corresponds to
the minimum
reference feedback
AN-25 Terminal 54 High Ref./Feedb. Value
Range:
Function:
1500.000 Referen-
ceFeedbackUnit
*
[-999999.999 -
999999.999
ReferenceFeed-
backUnit]
Enter the analog
input scaling value
that corresponds to
the maximum
reference feedback
value set in
AN-26 Terminal 54 Filter Time Constant
Range:
Function:
0.001 s
*
[0.001 - 10
s]
NOTE
This parameter cannot be adjusted
while the motor is running.
Enter the time constant. This is a first-
order digital low pass filter time constant
for suppressing electrical noise in terminal
54. A high time constant value improves
dampening but also increases the time
delay through the filter.
3.8.4 AN-3# Analog Input X30/11
Parameters to configure the scaling and limits for Analog
Input 1 associated with OPCGPIO General Purpose Field
Installed Option Module.
AN-30 Terminal X30/11 Low Voltage
Range:
Function:
0.07 V
*
[0 - par. AN-31
V]
Sets the analog input scaling value to
correspond to the low reference/
feedback value (set in
).
AN-31 Terminal X30/11 High Voltage
Range:
Function:
10 V
*
[par. AN-30 - 10
V]
Sets the analog input scaling value to
correspond to the high reference/
feedback value (set in
Parameter Descriptions
AF-650 GP Programming Guide
DET-618C
73