No.
Description
Warning
Alarm/Trip
Alarm/Trip Lock
Parameter
Reference
64
Voltage Limit
X
65
Control Board Over-temperature
X
X
X
66
Heat sink Temperature Low
X
67
Option Module Configuration has Changed
X
69
Pwr. Card Temp
X
X
70
Illegal Drive configuration
X
75
Illegal Profile Sel.
X
76
Power Unit Setup
X
77
Reduced power mode
X
78
Tracking Error
(X)
(X)
79
Illegal PS config
X
X
80
Drive Restored to Factory Settings
X
81
CSIV corrupt
X
82
CSIV parameter error
X
83
Illegal Option Combination
X
88
Option Detection
X
91
Analog input 54 wrong settings
X
S202
246
Pwr.card supply
250
New spare parts
X
251
New Type Code
X
X
Table 5.1 Alarm/Warning Code List
(X) Dependent on parameter
1) Cannot be Auto reset via H-04 Auto-Reset (Times)
A trip is the action following an alarm. The trip coasts the
motor and is reset by pressing [Reset] or by a digital input
(parameter group E-1# [1]). The origin event that caused
an alarm cannot damage the frequency converter or cause
dangerous conditions. A trip lock is an action when an
alarm occurs, which could damage the frequency converter
or connected parts. A trip lock situation can only be reset
by a power cycling.
Warning
yellow
Alarm
flashing red
Trip locked
yellow and red
Table 5.2 LED Indication
Bit
Hex
Dec
Alarm Word
Alarm Word 2
Warning Word
Warning
Word 2
Extended
Status Word
Alarm Word Extended Status Word
0
00000001
1
Brake Check (A28) ServiceTrip,
Read/Write
Brake Check (W28)
reserved
Ramping
1
00000002
2
Pwr. Card Temp
(A69)
ServiceTrip,
(reserved)
Pwr. Card Temp (W69)
reserved
Auto Tune Running
2
00000004
4
Earth Fault (A14)
ServiceTrip,
Typecode/
Sparepart
Earth Fault (W14)
reserved
Start CW/CCW
3
00000008
8
Ctrl.Card Temp
(A65)
ServiceTrip,
(reserved)
Ctrl.Card Temp (W65)
reserved
Slow Down
4
00000010
16
Ctrl. Word TO
(A17)
ServiceTrip,
(reserved)
Ctrl. Word TO (W17)
Catch Up
5
00000020
32
Over Current
(A13)
reserved
Over Current (W13)
reserved
Feedback High
6
00000040
64
Torque Limit
(A12)
reserved
Torque Limit (W12)
reserved
Feedback Low
Troubleshooting
AF-650 GP Programming Guide
164
DET-618C
5
5