F-12 Motor Thermistor Input
Option:
Function:
NOTE
This parameter cannot be adjusted
while the motor is running.
Select the input to which the thermistor
(PTC sensor) should be connected. An
analog input option [1] or [2] cannot be
selected if the analog input is already in
use as a reference source (selected in
F-01 Frequency Setting 1
,
C-30 Frequency
Command 2
or
C-34 Frequency Command
3
).
[0]
*
None
[1]
Analog Input 53
[2]
Analog Input 54
[3]
Digital input 18
[4]
Digital input 19
[5]
Digital input 32
[6]
Digital input 33
NOTE
Digital input should be set to
[0] PNP - Active at 24 V
in
E-0#.
F-15 Motor Speed High Limit [Hz]
Range:
Function:
60.0
Hz
*
[par.
F-16 -
par. F-03
Hz]
Enter the maximum limit for motor speed.
The Motor Speed High Limit can be set to
correspond to the manufacturer’s
recommended maximum of the motor shaft.
The Motor Speed High Limit must exceed the
in
F-16 Motor Speed Low Limit [Hz]
. Only
F-17 Motor Speed High Limit [RPM]
or
F-15 Motor Speed High Limit [Hz]
will be
displayed depending on other parameters in
the Main Menu and depending on default
settings dependant on global location.
NOTE
Max. output frequency cannot exceed 10% of the carrier
frequency (
F-26 Motor Noise (Carrier Freq)
).
F-16 Motor Speed Low Limit [Hz]
Range:
Function:
0 Hz
*
[0 - par.
F-15 Hz]
Enter the minimum limit for motor speed.
The Motor Speed Low Limit can be set to
correspond to the minimum output
frequency of the motor shaft. The Motor
Speed Low Limit must not exceed the
setting in
F-15 Motor Speed High Limit [Hz]
F-17 Motor Speed High Limit [RPM]
Range:
Function:
3600
RPM
*
[par. F-18 -
60000 RPM]
Enter the maximum limit for motor
speed. The Motor Speed High Limit can
be set to correspond to the
manufacturer’s maximum rated motor
speed. The Motor Speed High Limit
must exceed the setting in
NOTE
Max. output frequency cannot exceed 10% of the carrier
frequency (
F-26 Motor Noise (Carrier Freq)
F-18 Motor Speed Low Limit [RPM]
Range:
Function:
0 RPM
*
[0 - par.
F-17 RPM]
Enter the minimum limit for motor speed.
The Motor Speed Low Limit can be set to
correspond to the manufacturer’s
recommended minimum motor speed. The
Motor Speed Low Limit must not exceed
the setting in
.
3.3.4 F-2# Fundamental 2
Parameters to configure drive Start Speed, Start Current,
Holding Time and Motor Noise (Carrier Frequency).
F-20 PM Start Mode
Option:
Function:
[0]
Rotor
Detection
Suitable for all applications where the motor
is known to be standing still when starting
(e.g. conveyors, pumps and non wind milling
fans).
[1]
*
Parking
If the motor turns at a slight speed (i.e.
lower than 2-5% of the nominal speed) e.g.
due to fans with light wind milling, select
[1]
Parking
and adjust
B-06 Parking Current
and
B-07 Parking Time
accordingly.
F-22 Start Speed [RPM]
Range:
Function:
0 RPM
*
[0 - 600
RPM]
Set a motor start speed. After the start
signal, the output speed leaps to set value.
Set the start function in
to
[3] Start speed cw
,
[4] Horizontal operation
or
[5] Adv. Vector Control/Flux Clockwise
, and
set a start delay time in
Parameter Descriptions
AF-650 GP Programming Guide
36