Figure 2.17 Control Wiring Access for IP55/ Nema 12 and IP66 /
Nema 4/4X Indoor
2.5.5.2 Control Terminal Types
and shows the removable adjustable frequency
drive connectors. Terminal functions and default settings
are summarized in
Figure 2.18 Control Terminal Locations
Figure 2.19 Terminal Numbers
•
Connector 1 provides four programmable digital
inputs terminals, two additional digital terminals
programmable as either input or output, a 24 V
DC terminal supply voltage, and a common for
optional customer supplied 24 V DC voltage. A
digital input for STO (Safe Torque Off) function.
•
Connector 2 terminals (+)68 and (-)69 are for an
RS-485 serial communications connection
•
Connector 3 provides two analog inputs, one
analog output, 10 V DC supply voltage, and
commons for the inputs and output
•
Connector 4 is a USB port available for use with
the DCT-10
•
Also provided are two Form C relay outputs that
are in various locations depending upon the
adjustable frequency drive configuration and size
•
Some options available for ordering with the unit
may provide additional terminals. See the manual
provided with the equipment option.
See
for terminal ratings details.
Terminal description
Terminal
Parameter
Default
setting
Description
Digital inputs/outputs
12, 13
-
+24 V DC
24 V DC supply
voltage. Maximum
output current is 200
mA total for all 24 V
loads. Usable for
digital inputs and
external transducers.
18
E-01
[8] Start
Digital inputs.
19
E-02
[10] Reversing
32
E-05
[0] No
operation
33
E-06
[0] No
operation
27
E-03
[0] No
operation
Selectable for either
digital input or
output. Default setting
is input.
29
E-04
[14] JOG
20
-
Common
for
digital
inputs and 0 V
potential for 24 V
supply.
37
-
Safe Torque
Off (STO)
Safe input. Used for
STO.
Analog inputs/outputs
39
-
Common for analog
output
Installation
AF-650 GP
TM
Design and Installation Guide
DET-767A
2-11
2
2
Содержание AF-650 GP Series
Страница 3: ...Safety AF 650 GPTM Design and Installation Guide DET 767A ...
Страница 9: ...Contents AF 650 GPTM Design and Installation Guide DET 767A ...
Страница 19: ...Introduction AF 650 GPTM Design and Installation Guide 1 10 DET 767A 1 1 ...
Страница 35: ...Installation AF 650 GPTM Design and Installation Guide 2 16 DET 767A 2 2 ...
Страница 41: ...Start Up and Functional Tes AF 650 GPTM Design and Installation Guide 3 6 DET 767A 3 3 ...
Страница 55: ...About Programming AF 650 GPTM Design and Installation Guide 5 10 DET 767A 5 5 ...
Страница 91: ...Application Setup Examples AF 650 GPTM Design and Installation Guide 6 36 DET 767A 6 6 ...
Страница 103: ...Status Messages AF 650 GPTM Design and Installation Guide 8 4 DET 767A 8 8 ...
Страница 123: ...Warnings and Alarms AF 650 GPTM Design and Installation Guide 10 10 DET 767A 10 0 ...
Страница 127: ...Basic Troubleshooting AF 650 GPTM Design and Installation Guide 11 4 DET 767A 11 1 ...
Страница 129: ...Terminal and Applicable Wir AF 650 GPTM Design and Installation Guide 12 2 DET 767A 12 2 ...
Страница 161: ...Specifications AF 650 GPTM Design and Installation Guide 13 32 DET 767A 13 3 ...