Abbrev. Ref.
Description
Cat.
EN 954-1
Category, level “B, 1-4”
FIT
Failure In Time: 1E-9 hours
HFT
IEC 61508
Hardware Fault Tolerance: HFT = n means,
that n+1 faults could cause a loss of the
safety function
MTTFd
EN ISO
13849-1
Mean Time To Failure - dangerous. Unit:
years
PFH
IEC 61508
Probability of Dangerous Failures per
Hour. This value shall be considered if the
safety device is operated in high demand
(more often than once per year) or
continuous mode of operation, where the
frequency of demands for operation made
on a safety-related system is greater than
one per year.
PL
EN ISO
13849-1
Discrete level used to specify the ability of
safety related parts of control systems to
perform a safety function under
foreseeable conditions. Levels a-e
SFF
IEC 61508
Safe Failure Fraction [%]; Percentage part
of safe failures and dangerous detected
failures of a safety function or a
subsystem related to all failures.
SIL
IEC 61508
Safety Integrity Level
STO
EN
61800-5-2
Safe Torque Off
SS1
EN 61800
-5-2
Safe Stop 1
Table 6.24 Abbreviations related to Functional Safety
The PFDavg value (Probability of Failure on Demand)
Failure probability in the event of a request of the safety
function.
6.10.1.1 Terminal 37 Safe Stop Function
Safe stop disables the control voltage of the power
semiconductors of the adjustable frequency drive output
stage which in turn prevents generating the voltage
required to rotate the motor. When the Safe Stop (T37) is
activated, the adjustable frequency drive issues an alarm,
trips the unit, and coasts the motor to a stop. Manual
restart is required. The safe stop function can be used for
stopping the adjustable frequency drive in emergency stop
situations. In the normal operating mode when safe stop is
not required, use the adjustable frequency drives regular
stop function instead. When automatic restart is used – the
requirements according to ISO 12100-2 paragraph 5.3.2.5
must be fulfilled.
Liability Conditions
It is the responsibility of the user to ensure personnel
installing and operating the Safe Stop function:
•
Read and understand the safety regulations
concerning health and safety/accident prevention
•
Have a good knowledge of the generic and safety
standards applicable to the specific application
User is defined as: integrator, operator, servicing,
maintenance staff.
Standards
Use of safe stop on terminal 37 requires that the user
satisfies all provisions for safety including relevant laws,
regulations and guidelines. The optional safe stop function
complies with the following standards.
EN 954-1: 1996 Category 3
IEC 60204-1: 2005 category 0 – uncontrolled stop
IEC 61508: 1998 SIL2
IEC 61800-5-2: 2007 – safe torque off (STO)
function
IEC 62061: 2005 SIL CL2
ISO 13849-1: 2006 Category 3 PL d
ISO 14118: 2000 (EN 1037) – prevention of
unexpected startup
Protective Measures
•
Safety engineering systems may only be installed
and commissioned by qualified and skilled
personnel
•
The unit must be installed in an IP54 cabinet or
in an equivalent environment. In special
applications, a higher IP degree may be necessary
•
The cable between terminal 37 and the external
safety device must be short circuit protected
according to ISO 13849-2 table D.4
•
If any external forces influence the motor axis
(e.g. suspended loads), additional measures (e.g. a
safety holding brake) are required in order to
eliminate hazards.
Application Setup Examples
AF-650 GP
TM
Design and Installation Guide
6-30
DET-767A
6
6
Содержание AF-650 GP Series
Страница 3: ...Safety AF 650 GPTM Design and Installation Guide DET 767A ...
Страница 9: ...Contents AF 650 GPTM Design and Installation Guide DET 767A ...
Страница 19: ...Introduction AF 650 GPTM Design and Installation Guide 1 10 DET 767A 1 1 ...
Страница 35: ...Installation AF 650 GPTM Design and Installation Guide 2 16 DET 767A 2 2 ...
Страница 41: ...Start Up and Functional Tes AF 650 GPTM Design and Installation Guide 3 6 DET 767A 3 3 ...
Страница 55: ...About Programming AF 650 GPTM Design and Installation Guide 5 10 DET 767A 5 5 ...
Страница 91: ...Application Setup Examples AF 650 GPTM Design and Installation Guide 6 36 DET 767A 6 6 ...
Страница 103: ...Status Messages AF 650 GPTM Design and Installation Guide 8 4 DET 767A 8 8 ...
Страница 123: ...Warnings and Alarms AF 650 GPTM Design and Installation Guide 10 10 DET 767A 10 0 ...
Страница 127: ...Basic Troubleshooting AF 650 GPTM Design and Installation Guide 11 4 DET 767A 11 1 ...
Страница 129: ...Terminal and Applicable Wir AF 650 GPTM Design and Installation Guide 12 2 DET 767A 12 2 ...
Страница 161: ...Specifications AF 650 GPTM Design and Installation Guide 13 32 DET 767A 13 3 ...