1.1.21 Derating for Ambient Temperature
The ambient temperature measured over 24 hours should be at least 5 °C lower than the max. ambient temperature.
If the frequency converter is operated at high ambient temperature, the continuous output current should be decreased.
The frequency converter has been designed for operation at max 50 °C ambient temperature with one motor size smaller than nominal. Continuous operation
at full load at 50 °C ambient temperature will reduce the lifetime of the frequency converter.
1.1.22 Derating for Low Air Pressure
The cooling capability of air is decreased at low air pressure.
For altitudes above 2000 m, please contact GE .
Below 1000 m altitude no de-rating is necessary but above 1000 m the ambient temperature or the maximum output current should be decreased.
Decrease the output by 1% per 100 m altitude above 1000 m or reduce the max. ambient temperature by 1 degree per 200 m
1.1.23 Derating for Running at Low Speeds
When a motor is connected to at frequency converter, it is necessary to check that the cooling of the motor is adequate.
A problem may occur at low speeds in constant torque applications. Running continuously at low speeds – below half the nominal motor speed – may require
additional air cooling. Alternatively, choose a larger motor (one size up).
Ordering No
Description
KYPDACLP1
Keypad with potentiometer
RMKYPDACLP1
Remote Mounting Kit for Keypad incl. 3 m cable , IP21 rated
NEMA1ACLP1
Nema Type 1 kit for Unit Size M1
NEMA1ACLP2
Type 1 kit for Unit Size M2
NEMA1ACLP3
Type 1 kit for Unit Size M3
DEPLTACLP1
De-coupling plate kit for Unit Sizes M1 and M2
DEPLTACLP2
De-coupling plate kit for Unit Size M3
for M1 frame
RMACLP1
DIN rail mounting kit for M1 Unit Size
NEMA1ACLP4
Type 1 kit for Unit Size M4
NEMA1ACLP5
Type 1 kit for Unit Size M5
DEPLTACLP3
De-coupling plate kit for M4 and M5 frames
GE Line Filters and brake resistors are available upon request.