OPM_SGS_USM_M40_M50_2US_V010.doc
User Manual
SG Series 400 & 500 UL S2
3. Disconnect on all Units the Battery from the UPS by opening (Pos. O) the External Battery
Switch or Fuses.
•
Wait
5 minutes
for DC-Link Capacitors discharge.
4. Disconnect the Utility supply on all Units
.
•
Complete power shutdown will OFF the
LCD Display Panel
.
Synoptic Diagram of first unit
Synoptic Diagram of other units
END OF PROCEDURE
DANGER !
It will take 5 minutes for the DC capacitors to discharge.
Open only the front door, do not open any other part of the UPS.