User Manual
SG Series 400 & 500 UL S2
Example 5
:
An equivalent set of parameters for
Example 4
is.
Weekday
d1
- Saturday
d2
- Sunday
d3
- Monday
d4
- Tuesday
d5
- Wednesday
d6
- Thursday
d7
- Friday
eBoost START
00:00 00:00 18:00 18:00 06:00 09:00 12:00
eBoost STOP
23:59 20:00 18:00 06:00 06:00 09:00 13:00
eBoost START
eBoost STOP
The
eBoost™ Operation Mode
is active from 18:00 of weekday
d3 - Monday
until 06:00 of weekday
d4 -
Tuesday
(as indicated by the
eBoost STOP
time of weekday
d4 - Tuesday
).
The
eBoost STOP
time of weekday
d3 - Monday
has no effect as it is followed by the
eBoost STOP
time
of weekday
d4 - Tuesday
.
It can be, without change of meaning, any time between 18:00 and 23:59.
Similarly, the
eBoost™ Operation Mode
is active from 18:00 of weekday
d4 - Tuesday
until 06:00 of
weekday
d5 - Wednesday
.
The
eBoost START
time of weekday
d5 - Wednesday
has no effect as it is preceded by the
eBoost START
time of weekday
d4 - Tuesday
.
It can be, without change of meaning, any time between 00:00 and 06:00.
NOTE !
To avoid undesired
eBoost™ Operation Mode
, verify:
•
Date and Time (first page of parameter).
•
eBoost™
screen how many hours of
eBoost™ Operation Mode
have been selected
for each day of the week.
NOTE !
The
eBoost™ Operation Mode
will become active only if the
Load
is supplied from
the
Inverter
.