Specifications and Ordering Information
Part Number 141535-01
Rev. E (10/08)
Page 6 of 11
-40
°
C to +85
°
C (-40
°
F to +185
°
F)
Humidity
95%, noncondensing.
CE Mark Directives
EMC Directives
Declaration of
Conformity
134036
EN61000-6-4
Radiated
Emissions
EN 55011, Class A
Conducted
Emissions
EN 55011, Class A
EN61000-6-2
Electrostatic
Discharge
EN 61000-4-2, Criteria B
Radiated
Susceptibility
EN61000-4-3, Criteria A
Conducted
Susceptibility
EN61000-4-6, Criteria A
Radiated
Susceptibility
ENV 50140, Criteria A
Conducted
Susceptibility
ENV 50141, Criteria A
Electrical Fast
Transient
EN 61000-4-4, Criteria B
Surge
Capability
EN 61000-4-5, Criteria B
Magnetic Field
EN 61000-4-8, Criteria A
Power Supply
Dip
EN 61000-4-11, Criteria B
Radio
Telephone
ENV 50204, Criteria B
CE Mark
Low-Voltage
Directives
Declaration of
Conformity
134036
Safety
Requirements
EN6101001
Hazardous Area Approvals
CSA/NRTL/C
Approval Option
(01)
Class I, Div 2
Groups A, B, C, D
T4 @ Ta = -20
°
C to +65
°
C
(-4
°
F to +150
°
F)
Certification
Number
CSA 150268-1002151 (LR 26744)
Approval Option
(02)
When used with I/O module
ordering options with internal
barriers:
A/Ex nC[ia] IIC
Class I, Zone 2/(0)
Class I, Div I, Groups A,B,C,D
T4 @ Ta = -20
°
C to +65
°
C
(-45
°
F to +150
°
F)