background image

 

Specifications and Ordering Information 

Part Number 141535-01 

Rev. E (10/08) 

 

Page 2 of 11 

Specifications 

Inputs 

Signal 

Accepts from 1 to 4 proximity 
transducer signals. 

Input 
Impedance 

Standard I/O 

10 kΩ 

TMR I/O 

The effective impedance of three 
Bussed TMR I/O channels wired in 
parallel to one transducer is 50 
kΩ. 

Power 
Consumption 

7 watts typical 

Sensitivity 

Radial Vibration 

3.94 mV/µm (100 mV/mil) or  

7.87 mV/µm (200 mV/mil). 

Thrust 

3.94 mV/µm (100 mV/mil) or  

7.87 mV/µm (200 mV/mil). 

Eccentricity 

3.94 mV/µm (100 mV/mil) or  

7.87 mV/µm (200 mV/mil). 

Differential 
Expansion 

0.394 mV/µm (10 mV/mil) or  

0.787 mV/µm (20 mV/mil). 

REBAM 

40 mV/µm (1000 mV/mil) or  

80 mV/µm (2000 mV/mil). 

Outputs 

Front Panel 
LEDs 

OK LED 

Indicates when the 3500/40M is 
operating properly. 

TX/RX LED 

Indicates when the 3500/40M is 
communicating with other 
modules in the 3500 rack. 

Bypass LED 

Indicates when the 3500/40M is in 
Bypass Mode. 

Buffered 
Transducer 
Outputs 

The front of each monitor has one 
coaxial connector for each 
channel. Each connector is short-
circuit protected. 

Output 
Impedance 

550 Ω 

Transducer 
Power Supply 

-24 Vdc 

Signal Conditioning  

Note: Specified at +25 ºC (+77 ºF) unless otherwise noted

 

Radial Vibration 

Frequency 
Response 

Direct filter 

User programmable, 4 Hz to 4000 
Hz or 1 Hz to 600 Hz. 

Gap filter 

-3 dB at 0.09 Hz. 

Not 1X filter 

60 cpm to 15.8 times running 
speed. Constant Q notch filter. 
Minimum rejection in stopband of  
-34.9 dB. (See Note that follows) 

Smax 

0.125 to 15.8 times running 
speed. (See Note that follows) 

1X and 2X 
Vector filter 

Содержание 3500/40M

Страница 1: ...hrust Position Differential Expansion Eccentricity REBAM Note The monitor channels are programmed in pairs and can perform up to two of these functions at a time Channels 1 and 2 can perform one function while channels 3 and 4 perform another or the same function The primary purpose of the 3500 40M monitor is to provide 1 Machinery protection by continuously comparing monitored parameters against ...

Страница 2: ...V mil Outputs Front Panel LEDs OK LED Indicates when the 3500 40M is operating properly TX RX LED Indicates when the 3500 40M is communicating with other modules in the 3500 rack Bypass LED Indicates when the 3500 40M is in Bypass Mode Buffered Transducer Outputs The front of each monitor has one coaxial connector for each channel Each connector is short circuit protected Output Impedance 550 Ω Tr...

Страница 3: ...esponse Direct filter 3 dB at 15 6 Hz Gap filter 3 dB at 0 41 Hz Accuracy Within 0 33 of full scale typical 1 maximum REBAM Frequency response Spike User programmable from 0 152 to 8678 Hz Element User programmable for BPFO ranging from 0 139 to 3836 Hz High pass corner is 0 8x BPFO Low pass corner is 2 2x BPFO Rotor User programmable from 0 108 to 2221 Hz Direct Programmable from 3 906 to 14 2 Hz...

Страница 4: ...f full scale typical 1 maximum when input signal is at the center frequency of the proportional value s passband Phase 3 degrees error maximum Channels enabled Certain configurations allow the user to enable only one channel of a channel pair See discussion and graphs in the final pages of this datasheet Filter tracking stepping requires a valid speed signal Initial condition Nominal filter set us...

Страница 5: ...econds in 1 second intervals Danger From calculated minimum value to 400 seconds in 0 5 second intervals Static Values Static values are measurements used to monitor the machine The Proximitor Monitor returns the following static values Radial Vibration Direct Gap 1X Amplitude 1X Phase Lag 2X Amplitude 2X Phase Lag Not 1X Amplitude Smax Amplitude Thrust Position Direct Gap Differential Expansion D...

Страница 6: ... Conducted Susceptibility ENV 50141 Criteria A Electrical Fast Transient EN 61000 4 4 Criteria B Surge Capability EN 61000 4 5 Criteria B Magnetic Field EN 61000 4 8 Criteria A Power Supply Dip EN 61000 4 11 Criteria B Radio Telephone ENV 50204 Criteria B CE Mark Low Voltage Directives Declaration of Conformity 134036 Safety Requirements EN6101001 Hazardous Area Approvals CSA NRTL C Approval Optio...

Страница 7: ...0 kg 0 44 lb I O Module barrier Dimensions Height x Width x Depth 241 3 mm x 24 4 mm x 163 1 mm 9 50 in x 0 96 in x 6 42 in Weight 0 46 kg 1 01 lb Rack Space Requirements Monitor Module 1 full height front slot I O Modules 1 full height rear slot Ordering Information General The 3500 40M Module requires the following or later firmware and software revisions 3500 01 Software Version 2 50 3500 02 So...

Страница 8: ...External Termination ET Blocks 125808 01 Proximitor ET Block Euro Style Connectors 128015 01 Proximitor ET Block Terminal Strip Connectors 132242 01 Prox Seismic Bussed TMR ET Block Euro Style connectors 132234 01 Prox Seismic Bussed TMR ET Block Terminal Strip connectors Cables 3500 Transducer XDCR Signal to ET Block Cable 129525 AXXXX BXX A Cable Length 0 0 0 5 5 feet 1 5 metres 0 0 0 7 7 feet 2...

Страница 9: ... 08 Page 9 of 11 Graphs and Figures 1 Main module front view 2 Status LEDs 3 Buffered Transducer Outputs 4 I O modules 5 Barrier I O module Internal Termination 6 I O Module Internal Termination 7 I O Module External Termination 8 I O Module External Termination Figure 1 ...

Страница 10: ...umes that only one channel of a channel pair is enabled The maximum speed depends on the number of rolling elements in the bearing The graph assumes that the rotor low pass filter corner is set at 3 2X the shaft speed and the spike high pass filter corner is set at 4X the element pass frequency for the outer race BPFO 1 Channel Configuration 0 5000 10000 15000 20000 25000 30000 35000 40000 6 8 10 ...

Страница 11: ...5000 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 Number of Elements Max R PM Rotor Element Pass Spike Figure 3 Bently Nevada is a trademark of General Electric Company Copyright 1999 Bently Nevada LLC 1631 Bently Parkway South Minden Nevada USA 89423 Phone 775 782 3611 Fax 775 215 2873 www ge energy com bently All rights reserved ...