Specifications and Ordering Information 

Part Number 141535-01 

Rev. E (10/08) 

 

Page 3 of 11 

Constant Q Filter. Minimum 
rejection in stopband of -57.7 dB. 

Note:

 1X & 2X Vector, Not 1X, and Smax 

parameters are valid for machine speeds 
of 60 cpm to 60,000 cpm. Machines 
ramping up from a stop must reach 72 
cpm before reaching an OK state. 

Accuracy 

Direct and Gap 

Within ±0.33% of full-scale 
typical, ±1% maximum. 

1X and 2X 

Within ±0.33% of full-scale 
typical, ±1% maximum. 

Smax 

Within ±5% maximum. 

Not 1X 

±3% for machine speeds less 
than 30,000 cpm.  

±8.5% for machine speeds 
greater than 30,000 cpm. 

Thrust and 
Differential 
Expansion 

Frequency 
Response 

Direct filter 

-3 dB at 1.2 Hz. 

Gap filter 

-3 dB at 0.41 Hz. 

Accuracy 

Within ±0.33% of full-scale 
typical, ±1% maximum. 

Eccentricity 

Frequency 
response 

Direct filter 

-3 dB at 15.6 Hz. 

Gap filter 

-3 dB at 0.41 Hz. 

Accuracy 

Within ±0.33% of full-scale 
typical, ±1% maximum. 

REBAM 

Frequency 
response 

Spike 

User programmable from 0.152 to 
8678 Hz. 

Element 

User programmable for BPFO 
ranging from 0.139 to 3836 Hz. 
High-pass corner is 0.8x BPFO. 
Low-pass corner is 2.2x BPFO. 

Rotor 

User programmable from 0.108 to 
2221 Hz. 

Direct 

Programmable from 3.906 to 14.2 
Hz. Selection is determined by 
Spike and Rotor filters. 

Gap 

Programmable from 0.002 to 1.0 
Hz. Selection is determined by the 
Rotor filter. 

1X Vector filter 

The range of shaft speeds for 
which the value is valid is 
dependent upon the nominal 
Shaft Speed for which the 
channel is configured. The 
following table summarizes the 
relationship: 

 

Nominal Shaft 

Speed (Hz) 

Valid Speed 

Range (Hz) 

10 to <126 

0.071 to 160 

126 to <252 

0.133 to 330 

252 to <504 

0.25 to 660 

504 to <584 

0.50 to 750 

 

Note:

 If a multi-event gear or speed wheel 

generates the speed input, the resultant 

Содержание 3500/40M

Страница 1: ...hrust Position Differential Expansion Eccentricity REBAM Note The monitor channels are programmed in pairs and can perform up to two of these functions at a time Channels 1 and 2 can perform one function while channels 3 and 4 perform another or the same function The primary purpose of the 3500 40M monitor is to provide 1 Machinery protection by continuously comparing monitored parameters against ...

Страница 2: ...V mil Outputs Front Panel LEDs OK LED Indicates when the 3500 40M is operating properly TX RX LED Indicates when the 3500 40M is communicating with other modules in the 3500 rack Bypass LED Indicates when the 3500 40M is in Bypass Mode Buffered Transducer Outputs The front of each monitor has one coaxial connector for each channel Each connector is short circuit protected Output Impedance 550 Ω Tr...

Страница 3: ...esponse Direct filter 3 dB at 15 6 Hz Gap filter 3 dB at 0 41 Hz Accuracy Within 0 33 of full scale typical 1 maximum REBAM Frequency response Spike User programmable from 0 152 to 8678 Hz Element User programmable for BPFO ranging from 0 139 to 3836 Hz High pass corner is 0 8x BPFO Low pass corner is 2 2x BPFO Rotor User programmable from 0 108 to 2221 Hz Direct Programmable from 3 906 to 14 2 Hz...

Страница 4: ...f full scale typical 1 maximum when input signal is at the center frequency of the proportional value s passband Phase 3 degrees error maximum Channels enabled Certain configurations allow the user to enable only one channel of a channel pair See discussion and graphs in the final pages of this datasheet Filter tracking stepping requires a valid speed signal Initial condition Nominal filter set us...

Страница 5: ...econds in 1 second intervals Danger From calculated minimum value to 400 seconds in 0 5 second intervals Static Values Static values are measurements used to monitor the machine The Proximitor Monitor returns the following static values Radial Vibration Direct Gap 1X Amplitude 1X Phase Lag 2X Amplitude 2X Phase Lag Not 1X Amplitude Smax Amplitude Thrust Position Direct Gap Differential Expansion D...

Страница 6: ... Conducted Susceptibility ENV 50141 Criteria A Electrical Fast Transient EN 61000 4 4 Criteria B Surge Capability EN 61000 4 5 Criteria B Magnetic Field EN 61000 4 8 Criteria A Power Supply Dip EN 61000 4 11 Criteria B Radio Telephone ENV 50204 Criteria B CE Mark Low Voltage Directives Declaration of Conformity 134036 Safety Requirements EN6101001 Hazardous Area Approvals CSA NRTL C Approval Optio...

Страница 7: ...0 kg 0 44 lb I O Module barrier Dimensions Height x Width x Depth 241 3 mm x 24 4 mm x 163 1 mm 9 50 in x 0 96 in x 6 42 in Weight 0 46 kg 1 01 lb Rack Space Requirements Monitor Module 1 full height front slot I O Modules 1 full height rear slot Ordering Information General The 3500 40M Module requires the following or later firmware and software revisions 3500 01 Software Version 2 50 3500 02 So...

Страница 8: ...External Termination ET Blocks 125808 01 Proximitor ET Block Euro Style Connectors 128015 01 Proximitor ET Block Terminal Strip Connectors 132242 01 Prox Seismic Bussed TMR ET Block Euro Style connectors 132234 01 Prox Seismic Bussed TMR ET Block Terminal Strip connectors Cables 3500 Transducer XDCR Signal to ET Block Cable 129525 AXXXX BXX A Cable Length 0 0 0 5 5 feet 1 5 metres 0 0 0 7 7 feet 2...

Страница 9: ... 08 Page 9 of 11 Graphs and Figures 1 Main module front view 2 Status LEDs 3 Buffered Transducer Outputs 4 I O modules 5 Barrier I O module Internal Termination 6 I O Module Internal Termination 7 I O Module External Termination 8 I O Module External Termination Figure 1 ...

Страница 10: ...umes that only one channel of a channel pair is enabled The maximum speed depends on the number of rolling elements in the bearing The graph assumes that the rotor low pass filter corner is set at 3 2X the shaft speed and the spike high pass filter corner is set at 4X the element pass frequency for the outer race BPFO 1 Channel Configuration 0 5000 10000 15000 20000 25000 30000 35000 40000 6 8 10 ...

Страница 11: ...5000 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 Number of Elements Max R PM Rotor Element Pass Spike Figure 3 Bently Nevada is a trademark of General Electric Company Copyright 1999 Bently Nevada LLC 1631 Bently Parkway South Minden Nevada USA 89423 Phone 775 782 3611 Fax 775 215 2873 www ge energy com bently All rights reserved ...

Отзывы: