CHAPTER 6: SETPOINTS
S3 PROTECTION
350 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL
6–97
Figure 6-42: Wattmetric characteristic angle response
POWER PICKUP DELAY
Range: 0.00 to 300.00 s in steps of 0.01 s
Default: 0.20 s
This setpoint defines a definite time delay before the inverse time characteristic is
activated. If the curve selection is set as "Definite Time" the element operates after this
security time delay. If the curve selection is "Inverse" or one of the FlexCurves, the
element uses both the definite and inverse time timers sequentially. The definite time
timer specified by this setpoint, is used, and when it expires it releases the inverse time
timer for operation.