4–2
350 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL
A1 STATUS
CHAPTER 4: ACTUAL VALUES
A1 Status
Clock
PATH
:
ACTUAL VALUES > A1 STATUS > CLOCK
CURRENT DATE
Feb 23 2016
Range: Date in format shown
Indicates today’s date.
CURRENT TIME
09:17:12
Range: Time in format shown
Indicates the current time of day.
Contact inputs
PATH
:
ACTUAL VALUES > A1 STATUS > CONTACT INPUTS
CI #1 (52a) (Contact Input 1)
OFF
Range: Off, On
The status of this contact shows the breaker close/open state, when wired to a 52a
breaker auxiliary contact.
CI #2 (52b) (Contact Input 2)
OFF
Range: Off, On
The status of this contact shows the breaker close/open state, when wired to a 52b
breaker auxiliary contact.
CONTACT INPUT 3 to 10
OFF
Range: Off, On
Message displays the state of the contact input. The message “ON” indicates that the
contact input is energized, and message “OFF” indicates a de-energized contact.
Output relays
PATH
:
ACTUAL VALUES > A1 STATUS > OUTPUT RELAYS
TRIP (Output Relay #1)
OFF
Range: Off, On
The “ON” state of Output Relay #1 (TRIP) shows that a TRIP command has been sent to
the breaker.
CLOSE (Output Relay #2)
OFF
Range: Off, On
The “ON” state of Output Relay #2 (CLOSE) shows that a close command has been sent
to the breaker.