Location 3
Programming the Zones
(3 segments of numerical data)
Segment 1
Door Shunt Zone
Program the zone that will be monitored as a door for access control. This location must be programmed with a
valid zone for monitored access control functions to work properly. (Default is
0
)
Additionally, this zone must be configured in the control panel as an “access control” zone by
programming an unused Zone Type Characteristic in locations 111-169 (Seg 4, Opt 4).
Segment 2
Request To Exit (RTE) Zone
Program the zone that will be monitored to signal an RTE. If this segment is programmed with a valid zone and the
zone is faulted, the reader will activate its onboard relay output and send the RTE. (Default is
0
)
Additionally, this zone must be configured in the control panel as an RTE zone by programming an
unused Zone Type Characteristic in locations 111-169 (Seg 4, Opt 3).
Segment 3
Zone start number
Program the systems starting zone number for this ProxPad. Default value is 1 which sets it to show the zone
status of up to the first 8 zones of the partition that this ProxPad is programmed to. The starting zone can be any
zone number within the range of the control panel.
When the starting zone number is set above the last zone of the system, the zone indication LED’s will
remain OFF.
Location 4
Programming the Various Reader Timers
(4 segment of numerical data)
Segment 1
Scan Time
Enter the amount of time required to hold a card between beeps to activate the functions programmed in Location
0, Segments 2 and 3. This timer is timed in 1/100-second increments from 0 to 2.55 seconds. (Default is
100
= 1
second).
Segment 2
Relay Active Time
Enter the amount of time the onboard relay output is energized once activated. This timer is timed in 1/10 second
increments from 0 to 25.5 seconds. (Default is
10
= 10 seconds).
Segment 3
Door Fault Warning Time
Enter the amount of time a monitored zone (see Location 3, Segment 1) must be faulted before sounding a
warning (local buzzer). The door fault warning is timed in 1-second increments from 0 to 255 seconds. (Default is
30
= 30 seconds).
Segment 4
Door Fault Alarm Time
Enter the amount of time a monitored zone (see Location 3, Segment 1) must be faulted before sending an alarm
condition to the control panel. The door fault alarm is timed in 1-second increments from 0 to 255 seconds.
(Default is
60
= 60 seconds).
Location 5
Programming the Opening Time for Schedule 1
(2 segments of numerical data)
Segment 1
Program the hour of the opening time in 24-hour format. (Default is
8
= 8:00 AM)
Segment 2
Program the minutes after the hour of the opening time for Schedule 1. (Default is
0
)
NX-1750 Installation manual
Page 16
18/02/05