Installation
2.4
FireShield Technical Reference Manual
Jumper setup
Jumper
Name
Description
J2
Reserved
for future
use
N/A
J3
Zone 6 -
10
jumper
Sets the five LEDs to report alarms
in zones 6 - 10. [1]
J4
Zone 1- 5
jumper
Sets the five LEDs to report alarms
in zones 1 - 5. [1]
J5
Group
jumper
Allows two FSRZI-As to be
connected to the same panel and
set to the same zone output option.
Install the jumper on FSRZI-As in
only
one
of the two groups.
[1] Install only one zone jumper on J3 or J4.
Note:
For jumper location, refer to the FSRZI-A wiring
diagram.
Installation instructions
A single FSRZI-A can be mounted in a standard, single gang
electrical box (ANSI/NEMA OS1-1996) using the single gang
cover plate that is included. Up to three FSRZI-As with or
without an FSRSI can be mounted in an approved multiple
gang electrical box (ANSI/NEMA OS1-1996) with
appropriate two, three, or four gang cover plates (model
numbers FSAT-2, FSAT-3, or FSAT-4).
Caution:
Make sure all power is disconnected from the panel
before installing. Observe static-sensitive handling practices.
To install the FSRZI-A:
1. Verify that all field wiring is free of opens, shorts, and
ground faults.
2. Connect wires to the FSRZI-A as shown (see wiring
diagram).
3. Using the two plain machine screws provided, mount the
module to the electrical box.
Note:
If you are surface mounting the FSRZI-A, you must
install washers (provided) between the FSRZI-A and the
surface mount box.
4. Using the two white machine screws provided with the
faceplate, mount the faceplate to the module.
5. Connect the wires to the terminals in the control panel.
6. Program the FSRZI-A using the Find Annunciators
program option. Refer to Chapter 3 “Programming.”
Compatible electrical box
Installing the FSRZI-A in an electrical box
Wiring diagram
J5
J4
J3
J2
24 V out +
24 V out -
24V IN
- +
C IN
+ -
C OUT
+ -
24V OUT
- +
24 V in +
24 V in -
Communication in -
Communication in +
Communication out +
Communication out -
From control
panel or
previous
device
To next device
Notes
1. All wiring is supervised and power limited.
2. 24 V out (aux power) must be programmed as non-
resettable.
Содержание FireShield FS302
Страница 1: ...FireShield Technical Reference Manual P N 3100353 Rev 3 0 12MAY03...
Страница 10: ...System overview and operation 1 8 FireShield Technical Reference Manual...
Страница 40: ...Programming 3 18 FireShield Technical Reference Manual...
Страница 42: ...Maintenance 4 2 FireShield Technical Reference Manual...
Страница 60: ...Panel specifications D 2 FireShield Technical Reference Manual...
Страница 66: ...Index Z 4 FireShield Technical Reference Manual...
Страница 68: ......