Programming
3.14
FireShield Technical Reference Manual
28. Enter the call back phone number
Description: Specifies the phone number that is used for call
back.
Format: Up to 20 digits
Default: Blank
To enter the call back phone number:
1. Press Reset until the first digit of the phone number is
displayed.
2. Press Panel Silence to save and advance to the next digit.
The trouble buzzer sounds a long beep as confirmation.
3. Press Reset until the next digit is displayed.
4. Press Panel Silence to save and advance to the next digit.
5. Repeat steps 3 and 4 until all digits are entered.
Note:
If less than 20 digits are entered, press Panel
Silence again or Remote Disconnect to advance to the
next program option.
6. When you press Reset at the last digit (20th digit), the
system automatically advances you to the next program
option.
Event notification programming
Event notification programming determines where events are
sent. Events can be sent to the primary, secondary, or both
central monitoring stations (CMS), or you can choose not to
send the event at all.
To program event notification, follow these general steps:
1. Select CMS locations for event reporting
2. Enter the system trouble restore code
Note:
If you are only using one central monitoring station and
are using the default settings, no further programming is
required. You can exit from programming by removing the
program jumper.
The first event notification programming option after
completing “Select the restore option” is “Panel Tst Rcvr.”
Twenty-one event receiver locations must be programmed
using steps described below, under “Select CMS locations for
event reporting.”
CS Tst Rcvr
CS AB Tst Rcvr
Walk Tst Rcvr
Drill Rcvr
Reset Rcvr
Program Mode Rcvr
DACT Disab Rcvr
Panel Sil Rcvr
Signal Sil Rcvr
Grd Fault Rcvr
Low Batt Rcvr
Mis Batt Rcvr
Int Comm Tr Rcvr
AC Fail Rcvr
Charger Tr Rcvr
Xfrmr 2 Tr Rcvr
Aux Pwr Tr Rcvr
Periph Trb Rcvr
Line 1 Trb Rcvr
Line 2 Trb Rcvr
Delivery Tr Rcvr
After programming the receiver locations, continue with the
steps described under “Enter the system trouble restore code.”
1. Select CMS locations for event reporting
Description: Specifies which CMS receives each event.
Settings: None
CS
1
CS
2
CS 1 and 2
Default: CS 1
To select the CMS locations for event reporting:
1. Press Reset to select the desired CMS location.
2. Press Panel Silence to save and advance to the next
program option.
The trouble buzzer sounds a long beep as confirmation.
3. Repeat steps 1 and 2 to set the CMS location for each
option.
4. When you reach the last option, proceed to "Enter the
system trouble restore code" below.
2. Enter the system trouble restore code
Description: Sets the code that is transmitted to the CMS with
trouble restoral events.
Format: 1 digit (0 – 9 and A – F)
Default: See Appendix E “Default event codes.” This can be
changed if needed.
To enter the system trouble restore code:
1. Press Reset to increment the restore code if it needs to be
changed.
2. Press Panel Silence to save and advance to the next
program option.
The trouble buzzer sounds a long beep as confirmation.
Содержание FireShield FS302
Страница 1: ...FireShield Technical Reference Manual P N 3100353 Rev 3 0 12MAY03...
Страница 10: ...System overview and operation 1 8 FireShield Technical Reference Manual...
Страница 40: ...Programming 3 18 FireShield Technical Reference Manual...
Страница 42: ...Maintenance 4 2 FireShield Technical Reference Manual...
Страница 60: ...Panel specifications D 2 FireShield Technical Reference Manual...
Страница 66: ...Index Z 4 FireShield Technical Reference Manual...
Страница 68: ......