ESL 1500 Series Fire Alarm Control Panel

Field Wiring

Class A System Wiring Diagram

Connect to

120 V AC

60Hz

Connector from

transformer

Blk

Wht

Case

ground

Auxiliary

power(+)

Optional drill

test switch

Fire drill

1

6

7

8

Local Zone 1 alarm

(Supervised)

System 15VDC

System trouble

contacts

Auxiliary alarm

contacts

BMB standoff

9

10 11 12 13 14 15 16

17

18

19

20

21

22

23

24

Zone 1

Zone 1

alarm

System

trouble

AC

power

Connector from

24 V DC battery in

BMB

8-Not used
7-Not used
6-Not used

5-Zone 2 supervisory

4-Zone 1 remote annunciator

3-Silent walktest
2-Zone 1 waterflow
1-Alarm verification

1

2

RA

B+

A+

A-

B-

RA

B+

A+

A-

B-

LEM

ZEM

Zone 4 & 5

ZEM

Zone 2 & 3

System

GND

ON

1

2

3

4

5

6

7

8

+
+

-
-

+
+

-
-

429C

429C

2.7K EOL

Resistor 1/2W

Pull station

Heat sensor

2.7K EOL

Resistor

1/2W

-

-

+

+

449C

449C

Zone 2

Zone 3

Zone 4

Zone 5

-

-

+

+

-

-

+

+

-

-

+

+

2.7K EOL

Resistor

1/2W

204-12/24V
Power
supervision relay

2.7K EOL

Resistor 1/2W

RA

B+

A+

A-

B-

RA

B+

A+

A-

B-

B+   A+    A-    B-

B-

B+

A+

A-

B-

B+

A+

A-

Zone 1 is shown with 4-wire
detectors, wired in Class A (Style D)

C  N/O N/C C  N/C N/O

Power ON

(standby condition)

2.7K EOL

Resistor 1/2W

2.7K EOL

Resistor 1/2W

Zone 2 is shown with 2-wire
detectors, wired in Class A (Style D)

Zone 5 is shown with 2-wire heat
detectors and pull stations, wired in
Class A (Style D)

2.7K EOL

Resistor 1/2W

Bell circuit 1 is shown with Class  A
(Style Z) wiring

Figure 5. Class A System Wiring Diagram

Содержание 1501

Страница 1: ...ESL 1500 Series Fire Alarm Control Panel Installation and Operations Manual GE Security g...

Страница 2: ......

Страница 3: ...n 6 Supervisory Functions 6 Remote Test Drill 6 Field Wiring 7 Installation Recommendations Precautions 9 Field Wiring Checkout Procedures 10 Alarm Initiating Devices 10 Alarm Indicating Devices 11 Co...

Страница 4: ......

Страница 5: ...re 10 Terminal Connections 12 Figure 11 Local Energy Module LEM Wiring Diagram 13 Figure 12 BMB Default Settings 13 Figure 13 ZEM Default Settings 14 Figure 14 ZEM Programming Switches Location 14 Tab...

Страница 6: ...good mechanical and working order If any application or installation information is not understood or is not covered in this manual please contact Technical Support 800 648 7424 Sales 800 547 2556 Sy...

Страница 7: ...e panel 5 initiating circuits 2 indicating circuits 1500 BMB Basic Master Board 1 initiating circuit 2 indicating circuits 1500 ZEM Zone Expansion Module 2 initiating circuits Class A or B 1500 LEM Lo...

Страница 8: ...ies Determine the total system power requirements by using the Standby Battery Power Worksheet in Appendix B 9 System Check Make certain the 1500 panel is operating properly before connecting field wi...

Страница 9: ...at has not been disabled will activate the indicating devices as normal The zone disconnect switch is defeated when a zone has been programmed for waterflow service See BMB Programming Walktest makes...

Страница 10: ...en using alarm verification total alarm delay alarm verification smoke detector power up time cannot exceed 60 seconds according to the National Fire Alarm Code NFPA 72 or 30 seconds for installations...

Страница 11: ...red local alarm LED lights In addition the supervisory LED on the BMB will activate During supervisory trouble the integral sounder activates a rapidly pulsing tone zone 2 yellow local trouble LED lig...

Страница 12: ...1 Alarm verification 1 2 RA B A A B RA B A A B LEM ZEM Zone 4 5 ZEM Zone 2 3 System GND ON 1 2 3 4 5 6 7 8 429C 429C 2 7K EOL Resistor 1 2W Pull station Heat sensor 2 7K EOL Resistor 1 2W 449C 449C Z...

Страница 13: ...ktest 2 Zone 1 waterflow 1 Alarm verification 1 2 RA B A A B RA B A A B LEM ZEM Zone 4 5 ZEM Zone 2 3 System GND ON 1 2 3 4 5 6 7 8 429C 521B 429C 521B 2 7K EOL Resistor 1 2W Pull station Heat sensor...

Страница 14: ...em to a conduit or green wire circuit that also is used to power resistance heating motors fans air conditioning equipment or florescent lighting circuits since leakage currents into the ground return...

Страница 15: ...capable of protecting equipment from damage caused by direct hit strikes of lightning due to the extremely high energy released 10 million to 100 million volts 10 000 to 30 000 amps However line surge...

Страница 16: ...15 or 3 16 diameter drill and deburr 4 Install the supplied push rivets from the outside of the cabinet through both the cabinet side wall and the snap track driving the push pins flush with the rivet...

Страница 17: ...1 trouble Supervisory Low no AC Low no battery Ground fault Indicating 1 trouble Indicating 2 trouble 1 2 3 4 5 6 7 8 9 10 1 Mounting hole 2 Basic Master Board BMB 3 Housing backbox 4 Programming swi...

Страница 18: ...le LEM trip circuit is designed to interface to a Listed Master Box with a local energy trip mechanism This optional module provides a supervised trip circuit from the 1500 system that activates the M...

Страница 19: ...1500 BMB is disabled See Supervisory Functions 2 on zone 3 5 Remote Connection to remote indicator not supervised Annunciator 1 on zone 2 4 Remote Connection to remote indicator not supervised Annunci...

Страница 20: ...the batteries Maintenance Batteries The 1500 Series control unit uses two sealed lead acid batteries as the secondary power source The batteries must be replaced if the Low Battery LED remains on for...

Страница 21: ...o low upgrade or move to new circuit Low No AC power LowAC power If secondary shows less than 22 VAC replace transformer System trouble LED Less than 94 VAC at transformer primary no load Trouble soun...

Страница 22: ...e Y or Z Maximum current per circuit 1 0 Amps Maximum total current 1 5 Amps Output voltage 24 VDC FWR End of line 2 7 K Ohms 1 2 Watt Supplementary alarm trouble contacts System trouble 2 0 A 30 VDC...

Страница 23: ...tectors shown in Table 10 Table 8 Compatible Indicating Devices Manufacturer Part Number Amseco SLB24 75C Amseco SLB24G 75C Amseco SMS1 3A EST G1 R HOV110 EST G1 R HOV15 EST G1 R HOV75 EST G1 R V15 ES...

Страница 24: ...lity Identifier per Circuit Ohms Identifier ESL 400 Series 429C 429CT 100 C01 S10A 20 Self Diagnostic 429CRT 429CST 100 C01 S11A 20 ESL 500 Series 521B 521NB 100 C01 DIP SW 1 ON S09A 20 and ESL 500N S...

Страница 25: ...1000 mA mA Auxiliary System Power mA 1 Amp 1000 mA mA 1500 ZEM Zone 2 8 mA mA 70 mA mA 1500 ZEM Zone 3 8 mA mA 70 mA mA 1500 ZEM Zone 4 8 mA mA 70 mA mA 1500 ZEM Zone 5 8 mA mA 70 mA mA 1500 LEM 1 mA...

Страница 26: ...from any other zone is not affected Alarm Disconnect Switch Operated After Alarm Condition For Maintenance Use Only Auxiliary alarm relay contacts remain latched Alarm indicating circuits are turned O...

Страница 27: ......

Страница 28: ...2603 Rev J 04 04 64812687 Rev J Tech Support 800 648 7424 FaxBack 800 483 2495 www GESecurity com GE Security 12345 SW Leveton Drive Tualatin OR 97062 503 692 4052 USA Canada 800 547 2556 GE Security...

Отзывы: