QUICKSTART GUIDE
OVERVIEW
MM200 MOTOR MANAGEMENT SYSTEM – QUICKSTART GUIDE
5
CAUTIO
N
CAUTION:
MM200 is not to be used in any way other than described in this manual.
Figure 6: MM200 terminal connection overview
A Modbus RTU RS485 port, a thermistor input, and a 50:0.025 CBCT input are provided.
Profibus and Devicenet are provided as options.
Table 2: Slot position
Figure 7: MM200 terminal connection torque rating
CAUTIO
N
CAUTION:
Use gauge size appropriate for the voltage and current draw of the device.
Slot
Type
A
PSU/Inputs/Control Panel
B
CPU/CTs
C
Outputs/CBCT/Thermistor/RS485
Control Panel
Profibus or DeviceNet
Optional fieldbus protocols
888740A2.CDR
CTs
PSU
Inputs
RS485
Thermistor
CBCT
2 x Form A
1 x Form C
connector
screw torque
CT
4.5 lb-in
IPS, output
5.0 lb-in
Fieldbus,
3.0 lb-in
Thermistor & RS485