22
MM200 MOTOR MANAGEMENT SYSTEM – QUICKSTART GUIDE
SPECIFICATIONS
QUICKSTART GUIDE
THERMISTOR INPUTS
Sensor type:...........................................................Positive temperature coefficient PTC (
R
HOT
= 100 to
30000 ohms), negative temperature coefficient NTC (
R
HOT
=
100 to 30000 ohms)
Accuracy:................................................................±6% of reading or ±100 ohms, whichever is greater
1.5.3 Outputs specifications
OUTPUT RELAYS
Configuration: ......................................................electromechanical 2 x Form-A and 1 x Form-C
Contact material:................................................silver-alloy
Operate time:........................................................10 ms
Minimum contact load:....................................10 mA at 5 V DC
Maximum switching rate:...............................300 operations per minute (no load), 30 operations per
minute (load)
Mechanical life:....................................................10 000 000 operations
Continuous current:...........................................5 A at 60°C
Make and carry for 0.2s:..................................30 A per ANSI C37.90 (
not UL rated
)
OUTPUT RELAY BREAK CAPACITY (FORM-A RELAY)
AC resistive, 120 V AC: ......................................5 A
AC resistive, 250 V AC: ......................................5 A
AC inductive, PF = 0.4:.......................................240 VA pilot duty
DC resistive, 30 V DC:........................................5 A
OUTPUT RELAY BREAK CAPACITY (FORM-C RELAY)
AC resistive, 120 V AC: ......................................5 A normally-open, 5 A normally-closed
AC resistive, 240 V AC: ......................................5 A normally-open, 5 A normally-closed
AC inductive, PF = 0.4:.......................................240 VA pilot duty
DC resistive, 30 V DC:........................................5 A
1.5.4 Power supply specifications
POWER SUPPLY (LO RANGE)
Nominal:..................................................................24 V DC
Range:......................................................................18 to 36 V DC
Power Consumption:.........................................10 W typical
POWER SUPPLY (HI RANGE)
Nominal:..................................................................120 to 240 V AC; 125 to 250 V DC
Range:......................................................................60 to 300 V AC (50 and 60 Hz); 84 to 250 V DC
Power consumption:.........................................10 W typical
Voltage withstand:.............................................2 × highest nominal voltage for 10 ms
1.5.5 Communications specifications
DEVICENET (COPPER)
Modes: .....................................................................slave (125, 250, and 500 kbps)
Connector: .............................................................5-pin terminal
PROFIBUS (COPPER)
Modes: .....................................................................DP V0 slave, up to 1.5 Mbps
Connector: .............................................................5-pin terminal
RS485 PORT
Port:...........................................................................opto-isolated
Baud rates: ............................................................up to 115 kbps
Protocol:..................................................................Modbus RTU, half-duplex
Maximum distance:...........................................1200 m
Isolation: .................................................................2 kV
Содержание MM200
Страница 4: ...toc 2 MM200 MOTOR MANAGEMENT SYSTEM QUICKSTART GUIDE TABLE OF CONTENTS...
Страница 30: ...26 MM200 MOTOR MANAGEMENT SYSTEM QUICKSTART GUIDE MM200 ORDER CODES QUICKSTART GUIDE...
Страница 32: ...i 2 MM200 MOTOR MANAGEMENT SYSTEM QUICKSTART GUIDE INDEX...
Страница 33: ...Digital Energy Multilin SUMMARYOFCERTIFICATION...
Страница 34: ...MM200 MOTOR MANAGEMENT SYSTEM QUICKSTART GUIDE...