2
MM200 MOTOR MANAGEMENT SYSTEM – QUICKSTART GUIDE
OVERVIEW
QUICKSTART GUIDE
Figure 1: Single line diagram
Table 1: MM200 protection functions
1.1.1 Mechanical installation
This section describes the mechanical installation of the MM200 system, including
dimensions for mounting.
1.1.1.1 Dimensions
The MM200 is packaged in a fixed format divided into three specific sections.
The dimensions of the MM200 are shown below. Additional dimensions for mounting are
shown in the following sections.
RS485 - Modbus RTU
Profibus/DeviceNet
52
METERING
A
51R
49
37
46
50G
MOTOR
LOAD
Temperature
Thermistor
Phase CT 3
Ground CT 1
Power Fuse
BUS
MM200
MOTOR MANAGEMENT SYSTEM
Contactor
888739A2.CDR
LO: 7 inputs and 3 outputs
HI: 6 inputs and 3 outputs
LO: 24 V DC
HI: 84 to 250 V DC / 60 to 300 V AC
ANSI device
Description
37
Undercurrent and underpower
46
Current unbalance
49
Thermal overload
50G
Ground instantaneous overcurrent
51R
Locked/stalled rotor, mechanical jam