MM200 MOTOR MANAGEMENT SYSTEM – QUICKSTART GUIDE
SETPOINTS
QUICKSTART GUIDE
Motor FLA (Mandatory setpoint)
Range: 0.5 to 1000.0 amps in steps of 0.1
Default: OFF
This setpoint must be specified for motor protection. The value may be taken from the
motor nameplate data sheets.
Supply Frequency (Mandatory setpoint)
Range: 50 Hz, 60 Hz
Default: 60 Hz
This setpoint specifies the nominal system frequency.
Motor Rating (Mandatory setpoint)
Range: 0.3 to 1100.0 kW in steps of 0.1 or OFF
Default: OFF
This setpoint specifies the motor rating (or low speed motor rating for two-speed
starters) in kWs.
The following sections provide additional information for each starter type.
Figure 17: Typical starter timing
1.2.2.3 Current transformers
The following setpoints are available to configure the current and voltage transformers.
Contactor B Relay
Contactor A Relay
Pre-contactor
Starting
Running
St
ar
t
A
St
ar
t
B
St
ar
t
A
S
top
Motor Current
Fu
ll
Volta
g
e
N
o
n
-reversin
g
Contactor B Relay
Contactor A Relay
Pre-contactor
Starting
Running
Motor Current
Fu
ll
Volta
g
e
Reversin
g
Contactor B Relay
Contactor A Relay
Pre-contactor
Starting
Running
Motor Current
Two
Sp
eed
Sta
rter
P
T
P
P
T
T
P - Pre-contactor Time setting
T - Transfer Time setting
R - Ramp Down Time setting
888710A1.CDR
Содержание MM200
Страница 4: ...toc 2 MM200 MOTOR MANAGEMENT SYSTEM QUICKSTART GUIDE TABLE OF CONTENTS...
Страница 30: ...26 MM200 MOTOR MANAGEMENT SYSTEM QUICKSTART GUIDE MM200 ORDER CODES QUICKSTART GUIDE...
Страница 32: ...i 2 MM200 MOTOR MANAGEMENT SYSTEM QUICKSTART GUIDE INDEX...
Страница 33: ...Digital Energy Multilin SUMMARYOFCERTIFICATION...
Страница 34: ...MM200 MOTOR MANAGEMENT SYSTEM QUICKSTART GUIDE...