13-264
8 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE
CHAPTER 13: MODBUS MEMORY MAP
74475
0x86AA Minimum Voltage
0
150
1
x VT
F2
20
1
Y
74476
0x86AB Counter Mode
0
1
1
FC126
0
1
Y
74477
0x86AC Voltage Drops
1
10
1
F0
2
1
Y
74478
0x86AD Time for Voltage Drops
0
600000000
1
s
F13
2000
2
Y
74480
0x86AF Curve Limit 1
0
150
1
x VT
F2
0
1
Y
74481
0x86B0 Curve Limit 2
0
150
1
x VT
F2
0
1
Y
74482
0x86B1 Curve Limit 3
0
150
1
x VT
F2
30
1
Y
74483
0x86B2 Curve Limit 4
0
150
1
x VT
F2
30
1
Y
74484
0x86B3 Curve Limit 5
0
150
1
x VT
F2
90
1
Y
74485
0x86B4 Curve Limit 6
0
150
1
x VT
F2
100
1
Y
74486
0x86B5 Curve Limit 7
0
150
1
x VT
F2
100
1
Y
74487
0x86B6 Curve Limit 8
0
150
1
x VT
F2
100
1
Y
74488
0x86B7 Curve Limit 9
0
150
1
x VT
F2
100
1
Y
74489
0x86B8 Curve Limit 10
0
150
1
x VT
F2
100
1
Y
74490
0x86B9 Curve Time 1
0
600000000
1
s
F13
0
2
Y
74492
0x86BB Curve Time 2
0
600000000
1
s
F13
150
2
Y
74494
0x86BD Curve Time 3
0
600000000
1
s
F13
150
2
Y
74496
0x86BF Curve Time 4
0
600000000
1
s
F13
600
2
Y
74498
0x86C1 Curve Time 5
0
600000000
1
s
F13
1500
2
Y
74500
0x86C3 Curve Time 6
0
600000000
1
s
F13
2000
2
Y
74502
0x86C5 Curve Time 7
0
600000000
1
s
F13
2000
2
Y
74504
0x86C7 Curve Time 8
0
600000000
1
s
F13
2000
2
Y
74506
0x86C9 Curve Time 9
0
600000000
1
s
F13
2000
2
Y
74508
0x86CB Curve Time 10
0
600000000
1
s
F13
2000
2
Y
74510
0x86CD Block
0
0xC6CD00
1
FC142
0
2
Y
74512
0x86CF Output Relays
0
0xFFFFFFFF
1
FC198
0
2
Y
74514
0x86D1 Events
0
1
1
FC126
1
1
Y
74515
0x86D2 Targets
0
2
1
FC101
1
1
Y
UV Reactive Power 1
74730
0x87A9 Function
0
4
1
FC100
0
1
Y
74731
0x87AA Signal Input
0
1
1
FC286A 0
1
Y
74732
0x87AB Voltage Mode
0
1
1
FC260
1
1
Y
74733
0x87AC Pickup Voltage
0
150
1
x VT
F2
85
1
Y
74734
0x87AD Pickup Vars
1
65000
1
kvar
F0
25
1
Y
74735
0x87AE Curr Superv Level
0
20
1
x CT
F2
10
1
Y
74736
0x87AF Var Direction
1
2
1
FC164A 1
1
Y
74737
0x87B0 Pickup Delay
0
600000
1
s
F13
500
2
Y
74739
0x87B2 Dropout Delay
0
600000
1
s
F13
0
2
Y
74741
0x87B4 Output Relays
0
0xFFFFFFFF
1
FC198
0
2
Y
74743
0x87B6 Block
0
0xC6CD00
1
FC142
0x0000
2
Y
74745
0x87B8 Restore Function
0
3
1
FC100F 0
1
Y
74746
0x87B9 Min Voltage
0
150
1
x VT
F2
95
1
Y
74747
0x87BA Min Frequency
2000
6500
1
Hz
F2
5900
1
Y
74748
0x87BB Max Frequency
2000
6500
1
Hz
F2
6050
1
Y
74749
0x87BC Min Current
0
100
1
x CT
F2
10
1
Y
Modbus
Address
Hex
Address
Description
Min
Max
Step Units
Format
Code
Factory
Default
Size in
Words
8
5
0
8
6
9
8
8
9
8
4
5
Содержание 845
Страница 26: ...3 6 8 SERIES PROTECTIVE RELAY PLATFORM COMMUNICATIONS GUIDE REAL TIME CLOCK CHAPTER 3 TIME PROTOCOLS ...
Страница 40: ...4 14 8 SERIES PROTECTIVE RELAY PLATFORM COMMUNICATIONS GUIDE DNP IMPLEMENTATION CHAPTER 4 DNP PROTOCOL ...
Страница 54: ...6 10 8 SERIES PROTECTIVE RELAY PLATFORM COMMUNICATIONS GUIDE INTEROPERABILITY CHAPTER 6 IEC 60870 5 104 ...
Страница 86: ...8 24 8 SERIES PROTECTIVE RELAY PLATFORM COMMUNICATIONS GUIDE THE IEC 61850 CONFIGURATOR CHAPTER 8 IEC 61850 ...
Страница 788: ...14 294 8 SERIES PROTECTIVE RELAY PLATFORM COMMUNICATIONS GUIDE CHAPTER 14 FORMAT CODES ...
Страница 868: ...B 74 8 SERIES PROTECTIVE RELAY PLATFORM COMMUNICATIONS GUIDE PIXIT CHAPTER B IEC 61850 IMPLEMENTATION DETAILS ...