12-12
8 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE
USING THE MEMORY MAP
CHAPTER 12: ABOUT THE MODBUS MEMORY MAP
For example:
Phase A Current value on relay display: 183.594 A
Phase current values read from Phase A Current Modbus registers:
04F5 (31270): 0002
04F6 (31271): CD2A
Combine the two 16 bit values into a 32 bit unsigned value: 183594
Apply the decimal point rule (divide by 1000): 183.594 A
Reading Last Trip Target Messages
Target messages are read through the Modbus Target Message registers.
Table 12-11: Modbus Map entries, Targets
Follow these steps to obtain the Last Trip message:
1.
Read address 30273 (0x0110) to obtain the Target Count.
2.
Write the value obtained from Target Count register to select the Target Index register
at address, for example: 40230 (0x00E5). This will position the Target Message Index at
newest Target Message.
3.
Read the Target Cause register for the newest Target Message to obtain the Target
Message cause.
For example, here are 3 Target Messages, with a Target Count of 3.
In this example, the following values are read from the Target Registers:
In order to interpret the target messages, we need to refer to the appropriate function
codes:
For Target Index #1: Link Error Primary
The value in Target Message Register 0111(hex) is 0x0000.
1st 16 bits High Order Word of Long Value
2nd 16 bits Low Order Word of Long Value
unsigned 32 bits Unsigned Long Value
unsigned 32 bits Unsigned Long Value, 3 Decimal Places
Register: 31270
Register: 312701
0002
CD2A
183594
183.594
Modbus
Address
Hex
Address
Description
Min
Max
Step Units
Format
Code
Factory
Default
Size in
Words
8
5
0
8
6
9
8
8
9
8
4
5
30273
0x0110
Target Count
0
256
1
F0
0
1
Y Y Y Y
30766
0x0111
Target Cause
0
0xFFFFFFFF
1
FC134
0
2
Y Y Y Y
Target Index # 3
GND IOC 1 OP
Target Index # 2
GND IOC 1 PKP
Target Index # 1
Link Error Primary
Target Index # 3 Value:
0x00CO, 0xF202
Target Index # 2 Value:
0x00CO, 0xF201
Target Index # 1 Value:
0x0000, 0x0037
Содержание 845
Страница 26: ...3 6 8 SERIES PROTECTIVE RELAY PLATFORM COMMUNICATIONS GUIDE REAL TIME CLOCK CHAPTER 3 TIME PROTOCOLS ...
Страница 40: ...4 14 8 SERIES PROTECTIVE RELAY PLATFORM COMMUNICATIONS GUIDE DNP IMPLEMENTATION CHAPTER 4 DNP PROTOCOL ...
Страница 54: ...6 10 8 SERIES PROTECTIVE RELAY PLATFORM COMMUNICATIONS GUIDE INTEROPERABILITY CHAPTER 6 IEC 60870 5 104 ...
Страница 86: ...8 24 8 SERIES PROTECTIVE RELAY PLATFORM COMMUNICATIONS GUIDE THE IEC 61850 CONFIGURATOR CHAPTER 8 IEC 61850 ...
Страница 788: ...14 294 8 SERIES PROTECTIVE RELAY PLATFORM COMMUNICATIONS GUIDE CHAPTER 14 FORMAT CODES ...
Страница 868: ...B 74 8 SERIES PROTECTIVE RELAY PLATFORM COMMUNICATIONS GUIDE PIXIT CHAPTER B IEC 61850 IMPLEMENTATION DETAILS ...