Installing the System
Figure 9. Connecting a HIM to the Panel
Connecting Detection Devices to Panel
Zone Inputs
The panel comes with six factory programmed onboard har-
wire zones (see “Learn Sensors (Sensors)” on page 29 for
factory settings). Zone inputs 1 through 6 are supervised
using a 2k-ohm, end-of-line resistor (included with panel) at
the last device on the circuit.
Ìi
Install an end-of-line resistor on all unused, factory
programmed, onboard panel zones.
All six zones accept either normally open (N/O) or nor-
mally closed (N/C) detection devices (see Figure 10).
The maximum loop resistance for each zone input is 300
ohms, plus the 2k end-of-line (EOL) resistor.
Connecting Intrusion Detection Devices
Figure 10 shows the typical wiring for N/C and N/O door/
window intrusion detection.
Figure 10. Connecting N/C and N/O Intrusion
Detection Circuits
Figure 11 shows the typical wiring for Optex model RX-
040 (PI) PIR motion detectors. The minimum available
panel voltage for hardwired PIR motion detectors is 8.5
VDC (9.1 VDC for UL Listed systems).
Figure 11. Connecting a PIR Motion Detector
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
ZONE COM
M
ON
ZO
NE 1
ZO
NE 2
+
1
2
VDC (
R
ED
)
BUS A
(
G
RN)
BUS B
(
W
HT)
GND (
B
L
K
)
TO ZONE
INPUT
DEVICE
(SHARED COMMONS)
ZO
NE 3
ZO
NE 4
ZO
NE 5
ZONE COM
M
ON
ZONE COM
M
ON
ZO
NE 6
ZO
NE 7
ZONE COM
M
ON
ZO
NE 8
P A N E L T E R M I N A L S
3
4
5
6
+12V
A
B
GND
BUS
9
10
11
ZONE
1
ZCOM
ZONE
2
NORMALLY
OPEN
(N/O)
CONTACTS
IN PARALLEL
2k Ohm
EOL RESISTOR
49-454
2k Ohm
EOL RESISTOR
49-454
NORMALLY
CLOSED
(N/C)
CONTACTS
IN SERIES
P A N E L
T E R M I N A L S
8642G06A.DS4
12
13
ZONE
3
ZCOM
3
4
+12V
GND
2k Ohm EOL
RESISTOR 49-454
(LOCATE AT LAST
DEVICE)
Содержание CONCORD Express
Страница 49: ...50 Troubleshooting ...