25
Programming the Panel
Battery Restoral
(Reporting—Global)
(05005)
(Default = off) If this setting is on, the panel reports to the
central monitoring station (or pager) when the panel battery
is restored or replaced or when a wireless sensor reports a
battery replacement to the panel.
To turn Battery Restoral reports off or on:
With the display showing BATTERY RESTORAL OFF/
ON (current setting), press
1
(off) or
2
(on). The
display flashes the entered setting. Press
ƒ
and the
display shows the new setting.
Buffer Full Rpt
(Reporting—Global)
(05006)
(Default = off) When this setting is turned on, the panel
sends an “event buffer full” report to the central monitoring
station when the panel event buffer (memory) is nearly full.
To turn Buffer Full Report off or on:
With the display showing BUFFER FULL RPT OFF/
ON (current setting), press
1
(off) or
2
(on). The
display flashes the entered setting. Press
ƒ
and the
display shows the new setting.
Zone Restorals
(Reporting—Global)
(05007)
(Default = off) When this setting is on, the panel reports a
restoral to the central monitoring station (or pager) when
wireless or hardwire zones in alarm are reset or “restored”
before the alarm is canceled.
Ìi
As with all GE Interlogix panels, hardwire smoke
detectors connected to Concord or SnapCard
hardwire zones do not send restorals.
To turn Zone Restoral reporting off or on:
With the display showing ZONE RESTORALS OFF/
ON (current setting), press
1
(off) or
2
(on). The
display flashes the entered setting. Press
ƒ
and the
display shows the new setting.
Two Trip Error
(Reporting—Global)
(05008)
(Default = off) This setting works with the “Alarm Verify”
feature. If ALARM VERIFY is turned on, then the panel
waits for a second sensor trip before sending an alarm (see
“ALARM VERIFY” later in this section and “Appendix A:
Table A3. Sensor Group Characteristics”).
If TWO TRIP ERROR is also on and a second sensor trip
does not occur within a 4-minute time period, then the
panel sends an error report to the central monitoring station.
When this feature is turned off, the panel does not send
“two trip error” reports.
Ìi
For UL Listed systems, Two Trip Error must be
turned off.
To turn Two Trip Error off or on:
With the display showing TWO TRIP ERROR OFF/
ON (current setting), press
1
(off) or
2
(on). The
display flashes the entered setting. Press
ƒ
and the
display shows the new setting.
TP Panic RPT FMT
(Reporting—Global)
(05009)
(Default = off) This setting determines how the panel
formats touchpad panic alarms reports to the central station.
When this feature is on, touchpad panic alarms report using
the following 3-digit codes:
Auxiliary—597, Police—598, Fire—599
When turned off, touchpad panic alarms report using a 3-
digit code from 500 to 503 with the last digit identifying the
touchpad device number.
To turn TP Panic RPT FMT off or on:
With the display showing TP PANIC RPT FMT OFF/
ON (current setting), press
1
(off) or
2
(on). The
display flashes the entered setting. Press
ƒ
and the
display shows the new setting.
AC Failure
(Reporting—Global)
(05010)
(Default = off) When this setting is on, the panel reports to
the central station if AC power to the panel is out for 15
continuous minutes.
Ìi
For UL Listed systems, AC Failure must be turned
on.
To turn AC Failure reports off or on:
With the display showing AC FAILURE OFF/ON
(current setting), press
1
(off) or
2
(on). The display
flashes the entered setting. Press
ƒ
and the display
shows the new setting.