REMOTE TOXIC SENSOR TRANSMITTER WIRING (CH 2)
GASMAX II monitors with remote-mount toxic sensor transmitters are shipped in two pieces and sensor
wiring must be installed by the end user. When used with Channel 2, toxic sensor transmitters connect to
the Channel Two 4-20mA input on the right-hand side terminal strip of the I/O power supply board.
The 10-0233-420 I/O power supply board must be configured for 4-20mA input as shown below.
NOTE: Poured seals and rigid conduit are required if the remote sensor is installed in a hazardous area.
IMPORTANT
: TOXIC SENSORS MAY FAIL TO OPERATE PROPERLY IF POWER IS NOT APPLIED WITHIN 6
MONTHS OF SHIPMENT. CONTACT GDS CORP FOR RECOMMENDATIONS IF THIS SITUATION MAY OCCUR.
Figure 3-13: Remote Sensor Transmitter Connection