background image

 

 

      
 

 

>D@23(5$7,21,167$//$7,21$1'0$,17(1$1&(

 

2SHUDWLRQ

This is a microcontroller based device capable of monitoring the 
gas concentration in up to 4 different zones: for each of these a 
4 .. 20 mA transmitter can be wired for measurement and 
detection of either L.P.G., Methane or Carbon Monoxide (CO). 

After power-up the display shows the following information:

 

 

 ]RQH

]RQH 

 

             

 

 ),50:$5( 

 9(56,21QQQQQQ 

 

 ]RQH

]RQH

 

 
where ’ nnnnnn ’ is the firmware version installed in the device.  
This information will remain visible for about 2 seconds. After this 
time the main information will be displayed (example): 
 

 ]RQH

]RQH 

 

             

 

 *B&SB 

 *30$ 

 

 ]RQH

]RQH

 

 
Each zone provides the following information: 
The first letter from left explains the transmitter type wired to the 
central unit. 
The transmitters which can be wired to the central unit can be 
different for each zone; the detectable gases are the following: 

 

-  L.P.G.: 

 

 

display shows letter ’

*

’ 

-  Methane (CH

4

): 

 

display shows letter ’

0

’ 

-  Carbon Monoxide:   

display shows letter ’

&

’. 

 

Values displayed on the right, in % L.E.L. (in case L.P.G. or 
Methane transmitters are connected) or ppm (in case of Carbon 
Monoxide) are the actual gas concentration values measured by 
the transmitters. The last letter shown on the display for each zone 
indicates the actual state of the relevant transmitter as explained 
in the following: 

 

B

:

   Active state (measuring, normal operation). 

*

:

   Fault on the ’

*

’as transmitter (Iout=2 mA). 

)

:

   ’

)

’ault over the current loop (either short or open circuit 

between any of the sensor wires: Iout=0 mA ). 

3

  ’

3

’realarm state. 

$

:

   ’

$

’larm state. When ’

295

’ is shown in place of the 

concentration value, this means that the upper limit of the 
measuring range has been exceeded. The ’

295

’ state 

corresponds to an input current value above 20mA. 

 

3UHDODUPDQG$ODUPIXQFWLRQV

 

The central unit can manage separately the pre-alarm and alarm  
conditions through two distinct, Normally Open, output relays. 
In case the prealarm threshold is reached, the central unit enables 
the relevant relay, which, in turn, closes its output contacts. 
In case the alarm threshold state is reached the unit will also 
enable the alarm relay thus closing the relevant output contact. At 
the same time the central unit has stored the pre-alarm state first 
and the alarm state later: the date and hour when the last has 
happened will be retained in the central unit memory. 

In case the gas concentration returns below the pre-alarm 
threshold, the relevant relay will return to its normal operation 
state or not, according to how the prealarm relay operating mode 
was set in the configuration. 

 

1RWH

For compliance with the current performance standards the 

Alarm relay has always a latched operation and this mode cannot 
be modified by the user. Whenever either an Alarm situation (’A’) 
or an Overrange (’OVR’) situation is reached, this relay is kept 
energised together with the internal buzzer and the red led until 
the user intentionally presses for 3 seconds the ’ 

UHVHW

’ key. 

 

$X[LOLDU\UHOD\

The central unit features one additional relay with changeover 
contacts (SPDT) which can be activated according to events and 
operating modes set by the installer through the relevant menu. 

 

'LVSOD\RIWKHODVWDODUPVWDWH

The central unit can retain the date and hour of the last alarm 
event happened in each zone. 
These information can be read by the user at any time by pressing 
for 3 seconds the ’ 

UHVHW

 ’ key  when in main display screen, then 

pressing ’<’ or ’>’ keys to cycle through the zones.

 

 

(OHFWULFDO:LULQJV

The central unit is normally powered with 230V~ mains voltage. 
At terminals 6 and 7 the user can wire a battery backup system 
whose purpose is to grant full functionality to the central unit even 
in case of power failure (see section [m] for details). 
Normally Closed (NC) output of the auxiliary relay is available at 
terminals 15 and 16, while the Normally Open (NO) one is 
available at terminals 16 and 17. 
This output can be used either for driving ’general purpose’ loads 
as a siren or an flashing light or, with proper configuration of the 
relevant parameters, to drive a gas shut-off electrovalve. 
Moreover this central unit features two single pole relay contacts 
for each zone, one for prealarm and one for alarm.  
The number of transmitters which can be wired to the central unit 
is 4, each compliant with the 4..20 mA current loop system. 
In order to make electrical wirings please refer to the suggested 
wiring diagrams. Please also note that all the relay outputs of the 
central unit do not feed power to the loads. 
In other words all outputs are ’voltage free’, giving the user more 
freedom to use loads with several operating voltages. 

D

 :$51,1*

x

7KLV&HQWUDO8QLWLV127DSSURYHGIRULQVWDOODWLRQLQ$7(;

FODVVLILHG]RQHV

x

$OOZLULQJVZLWKUHPRWHVHQVRUVPXVWEHPDGHXVLQJZLUHV

ZLWK  PPð PLQLPXP FURVV VHFWLRQ DQG QR ORQJHU WKDQ

P'RQRWXVHVDPHGXFWIRUVLJQDOZLUHVDQGPDLQV

x

,QFDVHRILQVWDOODWLRQZKHUHVWURQJ(0&GLVWXUEDQFHVDUH

SUHVHQW LW LV KLJKO\ VXJJHVWHG WKH XVH RI VKLHOGHG FDEOHV

7KH VKLHOG PXVW EH FRQQHFWHG WR WKH *QG WHUPLQDO RI WKH

UHOHYDQW]RQHRQWKH&HQWUDO8QLWVLGHRQO\

x

7KHDSSOLDQFHPXVWEHZLUHGWRWKHHOHFWULFPDLQVWKURXJKD

VZLWFK FDSDEOH RI GLVFRQQHFWLQJ DOO SROHV LQ FRPSOLDQFH

ZLWK WKH FXUUHQW VDIHW\ VWDQGDUGV DQG ZLWK D FRQWDFW

VHSDUDWLRQRIDWOHDVWPPLQDOOSROHV

x

,QVWDOODWLRQDQGHOHFWULFDOZLULQJVRIWKLVDSSOLDQFHPXVWEH

PDGH E\ TXDOLILHG WHFKQLFLDQV DQG LQ FRPSOLDQFH ZLWK WKH

FXUUHQWWHFKQLFDODQGVDIHW\VWDQGDUGV

x

%HIRUHZLULQJWKHDSSOLDQFHEHVXUHWRWXUQWKHPDLQVSRZHU

R

G

Y

 S

00 M

B

P

4

 S

E

  019179A

0 20041

5*<60%3

 =21(6 *$6 '(7(&7,21 &(175$/ 81,7 :,7+

566(5,$/287387

x

 230V~ power supply 

x

 Controls up to 4 zones 

x

 Manages CO, L.P.G. and Methane (CH

4

) transmitters 

x

 Wide parameters configuration freedom 

x

 Last alarm conditions data retention 

x

 LCD backlight 2 x 16 characters display 

x

 9 modules DIN rail mount 

x

 RS232 serial output 

V

 

H

 

L

 

W

 

U

 

R

 

Q

 

9LD3URVGRFLPR

,%$66$12'(/*5$33$9,

7HO 

)D[ 

KWWSZZZVHLWURQLW

HPDLOLQIR#VHLWURQLW

F

 

Summary of Contents for RGY S00 MBP4

Page 1: ...e user intentionally presses for 3 seconds the UHVHW key X LOLDU UHOD The central unit features one additional relay with changeover contacts SPDT which can be activated according to events and operat...

Page 2: ...nge the settings of the available parameters for a proper operation of the gas detection system B SB Main screen example B 0 B press enter Pressing or cycles QWHU SZG through single digits UVW HQW Pre...

Page 3: ...as triggered Even in case the non latched mode is selected shoul a pre alarm event be triggered the relevant date and time is acquired it can be displayed by pressing for a few seconds the reset key R...

Page 4: ...rent date and hour is mandatory for the correct recording of the last alarm state This adjustment must be performed when the central unit is first operated from this moment on the unit will retain the...

Page 5: ...KHFN of the transfer function of the central unit and correct detection of the abnormal situations This can be done by disconnecting the sensors from inputs and forcing through a proper calibrator the...

Page 6: ...1 x 7KLV HQWUDO 8QLW LV 127 DSSURYHG IRU LQVWDOODWLRQ LQ 7 FODVVLILHG RQHV T 7 21 1 250 7 21 No additional information regarding any special nature of the device are needed In the view of a constant...

Page 7: ...erse powered when Off 6 Auxiliary relay power up status E Enable manual start operation press reset button D Disable automatic start operation SSSS Password of the central unit 5 CR character Carriage...

Page 8: ...ly for the central unit either from mains or from the eventual battery backup system DXOW LQGLFDWRU This indicator shows the presence of a fault in a remote sensor or in the wiring to the central unit...

Page 9: ...9DF This wiring diagram is valid for Normally Closed type electrovalve 6 6 DV VHQVRUV In this diagram remote sensors of the SGY series are used please refer to the sensor User Manual for additional in...

Page 10: ...9DF This wiring diagram is valid for Normally Closed type electrovalve 6 6 DV VHQVRUV In this diagram remote sensors of the SGY series are used please refer to the sensor User Manual for additional in...

Page 11: ...DV VHQVRUV In this diagram remote sensors of the SGY series are used please refer to the sensor User Manual for additional information LU H WUDFWRUV 9DF These are activated when the pre alarm relay in...

Page 12: ...elay in each single zone is activated FRXVWLF VLUHQV 9DF These are activated when the alarm relay in each single zone is activated AuxRL Auxiliary relay 3U 3U 3UH DODUP UHOD V Refer to proper paragrap...

Reviews: