GASMAX II Operation & Maintenance Manual, Revision 7.0
Page 39
OUTPUT SIMULATION
allows setting the 4-20mA output to virtually any desired value. This is useful for
checking responses of devices receiving the GASMAX II
’s
-20mA output.
RELAY TEST
allows the user to manually activate any of alarm relays independent of the presence of gas.
This is useful during troubleshooting or initial installation when an end-to-end test of relay functionality
must be done.
WARNING
: TARGET GAS MONITORING AND ALARM PROCESSING ARE NOT ACTIVE WHILE IN THIS MENU.
SYSTEM SECURITY PAGE
The System Security menu offers two levels of protection against operation by unauthorized personnel or
those with malicious intent.
Figure 7-10: System Security Menu
CONTACT NAME
is a 12 character ASCII field available for displaying a phone # or name of personal who
knows the Pass Code. Lost Pass Codes may be recovered by entering the locked security menu and
holding the UP key for 5 seconds. The 4-digit code appears near the bottom of the screen.
SECURE LEVEL
sets LOW, HIGH or OFF modes. A LOW level allows CAL MODE sensor calibrations but
requires the 4-digit Pass Code prior to altering menus. HIGH level locks the entire menu database and the
CAL Mode until the correct Pass Code is entered. LOW and HIGH security levels always allow static
viewing of configuration menus.
S Y S T E M S E C U R I T Y
C o n t a c t N a me
S e c u r e L e v e l L OW
P a s s C o d e
U n l o c k e d