7.3. All: 
- results of each system inspection acc. to section 6.3. of this instruction, 
- situation, when the A2 alarm state was generated along with actions taken by the personnel, 
- stoppage of unit’s supply for more than 3 months,  
- any observed unusual symptoms in system operation 

 

NEED TO BE included in the attached Periodical Control Protocol or otherwise you can lose warranty for system 
elements and the Manufacturer will be released from any responsibility for operation of the System.  

 

7.4.  After 5 years from the date of production absolutely change internal batteries and  

(for MDP-4(8,16).(Z,ZA,ZB)) the internal rechargeable battery for new ones. Paid service, provided by the 
Manufacturer.  

 

7.5. 

NOTE:

 any attempt of interference in the internal circuits of the MDP unit breaches the warranty 

conditions and causes blocking of the unit’s operation (the message on the display: “Blocked 

control unit. To unlock call to…“). Removal of the blocking can be performed 

only by GAZEX service (extra paid). 

 

7.6.  According to 2002/96/EC Directive on waste electrical and electronic equipment (WEEE), 

the waste unit (classified as group 9.5 equipment in accordance with the above Act) cannot 
be stored with other wastes. Therefore it was marked with a special symbol: 

 
 
 

8. STORAGE 

 

 

In order to care for the internal battery (and a possible rechargeable battery - in version MDP-4(8,16). 

(B,Z,ZA,ZB)), it is recommended to store the unit in dry locations with temperature within the range of 

+5

°

C to +35

°

C. A short-term (<2h/8h) storage in ambient temperature from 

-10

°

C do 45

°

C is permitted.

 

When storing the MDP-4(8,16).(B,Z,ZA,ZB) for a longer time, the internal battery should be 

recharged every 6 months. Recharging is performed by adding the 230V~ or 12V= voltage depending on MDP 
version (without detectors connected) for the period of at least 24 hours. After that time switch the power off. 

NOTE!!!

 To disable power supply in the unit in MDP-4(8,16).(B,ZB) version equipped with internal battery support, 

disconnect the external power supply with main switch, then press "OK" button located on the front panel and hold 
it down until you disable the MDP (for about 10 seconds). 

Internal battery service life is calculated at approximately 3 to 5 years (depending on operating conditions), 

and the internal memory backup battery - for 5 years from the date of manufacture. After 5 years from the date of 
manufacture replace the battery and the rechargeable battery with a new - exchange can be conducted only by the 
Manufacturer. 

 
 
 
 
 
 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

MDP-4(8,16)… Instruction Manual  

edition 6PU63en   

©gazex’2011 v1101

  

Page 23

 

/ 24

 

Содержание MDP-4

Страница 1: ...E This device is equipped with a function blocking in the case of interference in the internal circuits 1 General purpose and selection table page 2 2 Description and manner of connecting in the syste...

Страница 2: ...ich group of detectors alarm occurred in fact it creates two detection systems the MDP unit in version Z controls operation of two shut off valves and controls the efficiency of the wired connection o...

Страница 3: ...relay OUTPUTS 1 1 1 1 1 1 1 1 12V voltage alarm OUTPUTS 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 12V voltage insulated alarm INPUTS 2 2 2 2 2 2 2 2 High current 12V OUTPUT for control of shut off valve 2 2 2 S...

Страница 4: ...vel 2 alarm at output in zone 1 level 2 alarm at output in zone 2 pulses closing the valve at zone 1 output were generated pulses closing the valve at zone 2 output were generated level 1 alarm at ala...

Страница 5: ...R T M M ZAW1 ZAW2 S1 S2 A2 A1 A2 A1 A2 AWARIA FAULT STREFA ZONE S1 STREFA ZONE S2 S1 S2 WYJ CIA STYKOWE RELAYS GAZEX 2006 MDP 4 8 16 v U4 MD 8 16 v U4 WYJ NAP 12V I 0 2A OUT N L 01 02 03 04 05 06 07...

Страница 6: ...of alarm state from the damaged detector until manual reset of MDP forced by status of detectors at MDP inputs Description of MDP statuses Activation of outputs from a specific zone occurs when the n...

Страница 7: ...1m interrupted tone signalling of finished alarm continuous tone indication of the ongoing alarm or emergency optional without sound signalling SILENT MODE activated from the menu Supplying detectors...

Страница 8: ...ting DEX detectors with the hub TABLE 4 3 Selection of conduits for detectors depending on the model of detector with a semiconductor sensor nn infra red P nR catalytic Pn Conduit fig 2 2 Conductor s...

Страница 9: ...ng of the conduit in the gland should be solid enough to keep the conduit inside the MDP during the attempt of manual pulling it out and to prevent the conduit from transferring mechanical forces into...

Страница 10: ...3 power supply unit MDP 4 8 A or PS 6 MDP 16 A with the battery connected maintain proper polarization the unit is protected by inverted polarization to terminal 02 to terminal 01 TIME LOCK ACTIVATIO...

Страница 11: ...ailable functions 5 4 1 Detectors and alarm inputs perform the below features 01 2011 Control Unit MDP 8 U6 3 Serial number 00457328 Date of changes made to the software Type and version of the unit U...

Страница 12: ...elect correct option with U and D keys and confirm with OK key Additionally a selected option is currently displayed on the LCD screen To exit the settings select the Exit option with U and D keys and...

Страница 13: ...tputs of zone 1 are switched off That delay can be set within the range of 1 sec 15 minutes only when automatic shutdown of zone 1 inputs is selected 4 Outputs Off zone2 delay delay of switching outpu...

Страница 14: ...wer supply fault Udex1 9VDC Internal power supply fault Udex2 9VDC Control Unit reset Control Unit power on Control Unit power off Internal accumulator fault no charging Internal accumulator fault U 1...

Страница 15: ...he unit settings Losing the password will prevent subsequent modification of the unit by the user The password can only be unlocked by GAZEX service employees extra paid service 5 4 6 System settings...

Страница 16: ...ol 3 Operation parameters allows changing unit s functionality Change SERVICE MODE enabled disabled AUTO RESET enabled disabled CABLE HUB none connected Exit Change press a SERVICE MODE allows blockin...

Страница 17: ...ed with characters shown on the screen above The new password should be saved and secured This password will be required at each entrance to the administrator s settings Losing the password will preve...

Страница 18: ...s and units of detectors depending on the measured medium Measuring range scaled to 4 20 mA The accuracy of the threshold alarm adjustment Medium 0 100 meas range 1 undefined medium the default type 0...

Страница 19: ...t installation while switched on detectors should ndic ed with N sign on the LCD screen be i at Control of MDP unit s operation is conducted by means of the keyboard located in the front panel During...

Страница 20: ...nt accuracy of the unit detector and test mixture 6 3 2 For MDP Z Simultaneously with generation of the alarm state at the control output A2 of the corresponding zone two electromagnetic pulses on VAL...

Страница 21: ...turned off or main fuse damaged next to the main switch the unit supplied from internal battery turn the power on and reset the unit with OK button or change the fuse for identical one time delay cut...

Страница 22: ...N The MDP unit and DEX DG detectors are electronic devices devoid of operating moving parts They were built on the basis of very durable semiconductor elements Therefore maintenance is reduced to Peri...

Страница 23: ...t be stored with other wastes Therefore it was marked with a special symbol 8 STORAGE In order to care for the internal battery and a possible rechargeable battery in version MDP 4 8 16 B Z ZA ZB it i...

Страница 24: ...MDP 4 8 16 Instruction Manual edition 6PU63en gazex 2011 v1101 Page 24 24 NOTICE...

Отзывы: