PROBLEM?

 

Before you call the manufacturer of the system, check and compare the observed effects with the one described below 

6.5 TABLE of special 

unit states after

 the power has been switched off: 

EFFECT

 

WHY

 

What to do

 

after the power has been switched off 
- the lit green “POWER” LED, no 
messages on the LCD display or 
messages are illegible and delayed 

display or ambient temperature 
below 

0

°

 

wait for about 15 minutes until 
compensation of temperatures or to 
provide higher temperature of the 
ambient air 

after burn-in alarm states “

A1

” or “

A2

” 

are generated at detectors’ inputs, 
which last for a few dozen seconds, 
then “

H1

” or “

H2

” alarms decay 

with a long-term storage of DEX or 
low ambient temperature, the burn-
in period was longer than the 
expected 1 minute (for detectors of 
low levels of calibration) 

switch the unit off, enter the 
installer’s menu, extend the burn-in 
time  
(max. 20 minutes), exit the menu;  
 

after burn-in the detectors are in 
normal state, while after submitted to 
test gas erroneous alarms are 
generated  

too long “A” and “A16” connecting 
conduits; 

Reduce the length of “A” and “A16” 
connections; 

Pr

” emergency state at input to the 

detector  

damaged supply conductor  
in the “A” or “A16” conduit or 
shorting between conductors or 
improper polarization of supply  

change polarization of conductors,  
remove shorting between 
conductors or exchange in conduit 
„A” or „A16”; 
switch the unit of for 10 seconds 
and switch it on again  

S

” emergency state at input to the 

detector 

broken signal conductor 
in “A” or “A16” conduit  
or  
incorrect order of signalling 
conductors 

remove opening of conduits, correct 
order of conductors in conduit “A” or 
“A16” or exchange conduits; 
reset the unit with the “OK” button 

emergency state “

FVAC

”, 

“Power supply”

 diode pulsates  

(only in version B) 

no external 230V AC supply 
voltage, 
main switch turned off or main fuse 
damaged (next to the main switch) 

the unit supplied from internal 
battery - turn the power on and 
reset the unit with “OK” button 

 

or change the fuse (for identical 
one, time delay cut-out), perform 
the change with power off 

emergency state “

FVAC

”, 

the 

Power supply

 diode is constantly 

lit (only in version B) 

information on a break of external 
supply longer than 60 seconds 

reset the unit with the “OK” button. 

Emergency state “

FVDC

” 

- in version A denotes the drop of 
external supply voltage below 
10.5V or damage of external supply 
unit or connection cable “E” 

- repair the external supply unit or 
exchange the connection cable “E”
 

in alarm states signallers connected to 

“U=12V ALARM OUTPUTS

” do not 

work 

- shorting in the connecting conduit 
or a damaged signalling device - 
automatic reset fuses triggered; 
- service mode on 

- switch the unit power off; 
remove shorting in the conduit or fix 
the signalling device, switch the 
power on 
- switch the service mode off 

InA1

” or „

InA2

” emergency state 

voltage connected to

 12V alarm 

inputs 

on A2 and/or A1 terminal(s) 

(cascade connection) 

ALARM signal from external 
devices (parent detectors in normal 
state). Alarm inputs operate with 5-
second delay. 

valve(s) is/are not closing despite the 
fact that A2 state is generated and 
mechanical efficiency of the valve is 
checked 

too high resistance of connecting 
conduit with “M” valve(s) (too small 
section of conductors for a given 
length)  

change the conduit for a thicker one 
or install the second one (4 x 2.5

2

), 

connecting conductors in pairs 
parallel 

lack of possibility to establish 
transmission with the unit in Modbus 
RTU protocol 

incorrect configuration of 
communication parameters, 
incorrect unit address, damaged 
RS232-RS485 converter  

enter system settings menu, turn 
Modbus RTU Slave/Master on, set 
the proper slave address, check 
transmission parameters 

all lights and LCD display off 

- no power or the main switch is off   - switch the power on 

 

MDP-4(8,16)… Instruction Manual  

edition 6PU63en   

©gazex’2011 v1101

  

Page 21

 

/ 24

 

Содержание MDP-4

Страница 1: ...E This device is equipped with a function blocking in the case of interference in the internal circuits 1 General purpose and selection table page 2 2 Description and manner of connecting in the syste...

Страница 2: ...ich group of detectors alarm occurred in fact it creates two detection systems the MDP unit in version Z controls operation of two shut off valves and controls the efficiency of the wired connection o...

Страница 3: ...relay OUTPUTS 1 1 1 1 1 1 1 1 12V voltage alarm OUTPUTS 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 12V voltage insulated alarm INPUTS 2 2 2 2 2 2 2 2 High current 12V OUTPUT for control of shut off valve 2 2 2 S...

Страница 4: ...vel 2 alarm at output in zone 1 level 2 alarm at output in zone 2 pulses closing the valve at zone 1 output were generated pulses closing the valve at zone 2 output were generated level 1 alarm at ala...

Страница 5: ...R T M M ZAW1 ZAW2 S1 S2 A2 A1 A2 A1 A2 AWARIA FAULT STREFA ZONE S1 STREFA ZONE S2 S1 S2 WYJ CIA STYKOWE RELAYS GAZEX 2006 MDP 4 8 16 v U4 MD 8 16 v U4 WYJ NAP 12V I 0 2A OUT N L 01 02 03 04 05 06 07...

Страница 6: ...of alarm state from the damaged detector until manual reset of MDP forced by status of detectors at MDP inputs Description of MDP statuses Activation of outputs from a specific zone occurs when the n...

Страница 7: ...1m interrupted tone signalling of finished alarm continuous tone indication of the ongoing alarm or emergency optional without sound signalling SILENT MODE activated from the menu Supplying detectors...

Страница 8: ...ting DEX detectors with the hub TABLE 4 3 Selection of conduits for detectors depending on the model of detector with a semiconductor sensor nn infra red P nR catalytic Pn Conduit fig 2 2 Conductor s...

Страница 9: ...ng of the conduit in the gland should be solid enough to keep the conduit inside the MDP during the attempt of manual pulling it out and to prevent the conduit from transferring mechanical forces into...

Страница 10: ...3 power supply unit MDP 4 8 A or PS 6 MDP 16 A with the battery connected maintain proper polarization the unit is protected by inverted polarization to terminal 02 to terminal 01 TIME LOCK ACTIVATIO...

Страница 11: ...ailable functions 5 4 1 Detectors and alarm inputs perform the below features 01 2011 Control Unit MDP 8 U6 3 Serial number 00457328 Date of changes made to the software Type and version of the unit U...

Страница 12: ...elect correct option with U and D keys and confirm with OK key Additionally a selected option is currently displayed on the LCD screen To exit the settings select the Exit option with U and D keys and...

Страница 13: ...tputs of zone 1 are switched off That delay can be set within the range of 1 sec 15 minutes only when automatic shutdown of zone 1 inputs is selected 4 Outputs Off zone2 delay delay of switching outpu...

Страница 14: ...wer supply fault Udex1 9VDC Internal power supply fault Udex2 9VDC Control Unit reset Control Unit power on Control Unit power off Internal accumulator fault no charging Internal accumulator fault U 1...

Страница 15: ...he unit settings Losing the password will prevent subsequent modification of the unit by the user The password can only be unlocked by GAZEX service employees extra paid service 5 4 6 System settings...

Страница 16: ...ol 3 Operation parameters allows changing unit s functionality Change SERVICE MODE enabled disabled AUTO RESET enabled disabled CABLE HUB none connected Exit Change press a SERVICE MODE allows blockin...

Страница 17: ...ed with characters shown on the screen above The new password should be saved and secured This password will be required at each entrance to the administrator s settings Losing the password will preve...

Страница 18: ...s and units of detectors depending on the measured medium Measuring range scaled to 4 20 mA The accuracy of the threshold alarm adjustment Medium 0 100 meas range 1 undefined medium the default type 0...

Страница 19: ...t installation while switched on detectors should ndic ed with N sign on the LCD screen be i at Control of MDP unit s operation is conducted by means of the keyboard located in the front panel During...

Страница 20: ...nt accuracy of the unit detector and test mixture 6 3 2 For MDP Z Simultaneously with generation of the alarm state at the control output A2 of the corresponding zone two electromagnetic pulses on VAL...

Страница 21: ...turned off or main fuse damaged next to the main switch the unit supplied from internal battery turn the power on and reset the unit with OK button or change the fuse for identical one time delay cut...