gazex MDP-4 Скачать руководство пользователя страница 22

lack of possibility to establish RS232 
serial transmission between the unit 
and the computer 

incorrect configuration of serial 
communication parameters, 
incorrect number of serial port, 
blocking of serial port by other 
software, damaged transmission 
cable 

close other programs using serial 
port, change the number of serial 
port or repair transmission cable 

the “

FACC

” alarm state or valve(s) 

is/are not closing, despite the A2 state 
is generated and mechanical and 
electrical efficiency of the valve(s) is 
checked 

internal battery discharged 

leave the unit connected to mains 
for min. 24 hours (battery charging), 
repeat the attempt. 
If the result is negative again - see 
test below 

as above, charging the battery does 

not improve operation of MDP unit 

(situation possible after several years 

of operation).  

 
 
 

 

Conduct an additional testing of 
battery’s efficiency explicitly 
specifying its suitability, as below: 
1) prepare an efficient, charged gel 
battery 12V (min. 5Ah for alarm 
systems) or a car battery;  
2) disconnect the connecting circuit 
with the valve from “VALVE” 
terminal; 
3) connect battery clamps (neutral 
polarization) to cable ends twice, 
ONLY for a short moment (max. 0.5 
sec.), 
4) 

closing 

of the valve proves the 

necessity of change an internal 
battery for a new provided ONLY by 
the manufacturer;  
5) 

not closing 

the valve indicates 

other causes beyond the MDP unit 
(consult the Manufacturer) 
6) check the other valve (if 
connected) in a similar manner; 

 

In the case of observing the effects other than the above please contact your Authorized Distributor or the Manufacturer.   

 
 
 
 
 

7. MAINTENANCE / OPERATION

 

 

 The 

MDP 

unit and 

DEX/DG 

detectors are electronic devices devoid of operating moving parts. They were built on 

the basis of very durable semiconductor elements. Therefore, maintenance is reduced to Periodical System 
Inspection . 

 

7.1. Periodical System Inspection: 

♦ 

clean dust off of MDP unit’s cover, 

♦ 

check tightness of the transparent cover and gland ducts, 

♦ 

check if the shut-off valve is open! 

♦ 

notify all system users on the planned inspection or about planned cut-off of gas supply, 

♦ 

System test acc. to section 6.3. 

of this Instruction Manual. 

 

 

R

ECOMMENDED FREQUENCY OF 

MDP 

PERIODICAL INSPECTION

 

 

not less frequent than 

every 3 months

, is sufficient for testing 

electrical-measurement properties of the Gas Monitoring System.

 

 

♦ 

The Periodic System Inspection should also be performed each time after the occurrence of specific 
conditions in the system, i.e.: 

–  occurrence of extreme conditions, e.g. high gas concentration, high or very low temperature, high periodical 

dustiness or increase in humidity, 

–  presence of high concentration of other gases, whose presence was not foreseen in the supervised zone, 
–  long-term operation with alarm state active, 
–  after a power stoppage for more than 1 hour, 
–  after occurrence of overvoltage or strong disturbances in electrical installation, 
–  after conduct of repair works or installation works, which can influence functioning of the system or its 

configuration, etc. 

7.2. During operation avoid using mobile phones, radio-telephones or other sources of strong electromagnetic field 
in the direct vicinity of the MDP unit - their use can cause interferences of MDP unit’s operation and false alarms. 
 7.2.1 During operation MDP avoid temperatures above recommended threshold values (Chapter 3). 
 
 
 

MDP-4(8,16)… Instruction Manual  

edition 6PU63en   

©gazex’2011 v1101

  

Page 22

 

/ 24

 

Содержание MDP-4

Страница 1: ...E This device is equipped with a function blocking in the case of interference in the internal circuits 1 General purpose and selection table page 2 2 Description and manner of connecting in the syste...

Страница 2: ...ich group of detectors alarm occurred in fact it creates two detection systems the MDP unit in version Z controls operation of two shut off valves and controls the efficiency of the wired connection o...

Страница 3: ...relay OUTPUTS 1 1 1 1 1 1 1 1 12V voltage alarm OUTPUTS 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 12V voltage insulated alarm INPUTS 2 2 2 2 2 2 2 2 High current 12V OUTPUT for control of shut off valve 2 2 2 S...

Страница 4: ...vel 2 alarm at output in zone 1 level 2 alarm at output in zone 2 pulses closing the valve at zone 1 output were generated pulses closing the valve at zone 2 output were generated level 1 alarm at ala...

Страница 5: ...R T M M ZAW1 ZAW2 S1 S2 A2 A1 A2 A1 A2 AWARIA FAULT STREFA ZONE S1 STREFA ZONE S2 S1 S2 WYJ CIA STYKOWE RELAYS GAZEX 2006 MDP 4 8 16 v U4 MD 8 16 v U4 WYJ NAP 12V I 0 2A OUT N L 01 02 03 04 05 06 07...

Страница 6: ...of alarm state from the damaged detector until manual reset of MDP forced by status of detectors at MDP inputs Description of MDP statuses Activation of outputs from a specific zone occurs when the n...

Страница 7: ...1m interrupted tone signalling of finished alarm continuous tone indication of the ongoing alarm or emergency optional without sound signalling SILENT MODE activated from the menu Supplying detectors...

Страница 8: ...ting DEX detectors with the hub TABLE 4 3 Selection of conduits for detectors depending on the model of detector with a semiconductor sensor nn infra red P nR catalytic Pn Conduit fig 2 2 Conductor s...

Страница 9: ...ng of the conduit in the gland should be solid enough to keep the conduit inside the MDP during the attempt of manual pulling it out and to prevent the conduit from transferring mechanical forces into...

Страница 10: ...3 power supply unit MDP 4 8 A or PS 6 MDP 16 A with the battery connected maintain proper polarization the unit is protected by inverted polarization to terminal 02 to terminal 01 TIME LOCK ACTIVATIO...

Страница 11: ...ailable functions 5 4 1 Detectors and alarm inputs perform the below features 01 2011 Control Unit MDP 8 U6 3 Serial number 00457328 Date of changes made to the software Type and version of the unit U...

Страница 12: ...elect correct option with U and D keys and confirm with OK key Additionally a selected option is currently displayed on the LCD screen To exit the settings select the Exit option with U and D keys and...

Страница 13: ...tputs of zone 1 are switched off That delay can be set within the range of 1 sec 15 minutes only when automatic shutdown of zone 1 inputs is selected 4 Outputs Off zone2 delay delay of switching outpu...

Страница 14: ...wer supply fault Udex1 9VDC Internal power supply fault Udex2 9VDC Control Unit reset Control Unit power on Control Unit power off Internal accumulator fault no charging Internal accumulator fault U 1...

Страница 15: ...he unit settings Losing the password will prevent subsequent modification of the unit by the user The password can only be unlocked by GAZEX service employees extra paid service 5 4 6 System settings...

Страница 16: ...ol 3 Operation parameters allows changing unit s functionality Change SERVICE MODE enabled disabled AUTO RESET enabled disabled CABLE HUB none connected Exit Change press a SERVICE MODE allows blockin...

Страница 17: ...ed with characters shown on the screen above The new password should be saved and secured This password will be required at each entrance to the administrator s settings Losing the password will preve...

Страница 18: ...s and units of detectors depending on the measured medium Measuring range scaled to 4 20 mA The accuracy of the threshold alarm adjustment Medium 0 100 meas range 1 undefined medium the default type 0...

Страница 19: ...t installation while switched on detectors should ndic ed with N sign on the LCD screen be i at Control of MDP unit s operation is conducted by means of the keyboard located in the front panel During...

Страница 20: ...nt accuracy of the unit detector and test mixture 6 3 2 For MDP Z Simultaneously with generation of the alarm state at the control output A2 of the corresponding zone two electromagnetic pulses on VAL...

Страница 21: ...turned off or main fuse damaged next to the main switch the unit supplied from internal battery turn the power on and reset the unit with OK button or change the fuse for identical one time delay cut...

Страница 22: ...N The MDP unit and DEX DG detectors are electronic devices devoid of operating moving parts They were built on the basis of very durable semiconductor elements Therefore maintenance is reduced to Peri...

Страница 23: ...t be stored with other wastes Therefore it was marked with a special symbol 8 STORAGE In order to care for the internal battery and a possible rechargeable battery in version MDP 4 8 16 B Z ZA ZB it i...

Страница 24: ...MDP 4 8 16 Instruction Manual edition 6PU63en gazex 2011 v1101 Page 24 24 NOTICE...