4)
Factory settings
- this option restores default unit settings, i.e.:
a. Values of the signal detectors (4-20mA) scaled to 0-100% of range,
b. The alarm thresholds set appropriately A1=10% range, A2=30% range,
c. detectors off, assigned to the two zones "1+2",
d. alarm inputs assigned to the two zones "1 +2";
e. outputs set in auto mode;
f. The delay times set to default values;
g. unit’s operation mode - normal;
5)
Special Functions
– this option is password-protected, intended for special purposes.
Description of necessary functions is located in annexes appended to this instruction;
6)
Administrator password
- allows changing admin password.
Change administrator password
Enter old password:
*****
Enter new password:
*******
Repeat new password:
*******
Password should contain 2-8 characters
In order to change the password:
- enter old password,
- enter new password,
- repeat new password
After the new password has been correctly entered, a message “The password has been
changed” will be displayed. The password is a combination of “U”, “D”, “L” and “R” keys and
can contain from two to eight characters. When the password is being entered, it is masked
with characters shown on the screen above.
The new password should be saved and secured. This password will be required at
each entrance to the administrator’s settings. Losing the password will prevent
subsequent modification of the unit’s system settings! The password can only be
unlocked by GAZEX service (extra paid).
6. START-UP MDP
IN THE SYSTEM
6.1 After configuration is over (or configuration stage is omitted by the user), the MDP unit switches to
the detectors’ burn-in mode and signals that by means of a green power supply diode and a
message on the LCD screen.
PRE-HEATING
System starting,
Time left: 1 min 00 sec.
During pre-heating, duration of which is defined in the installer’s menu, operation points of individual
detectors need to be stabilized to operate properly. During this stage all alarm states and
emergency states are blocked.
6.2 After pre-heating the MDP switches to normal operation. The LCD screen in real time signals
statuses of inputs of detectors and alarm inputs, statuses of outputs and critical parameters of MDP
unit’s operation.
“Threshold screen” - displays information on current alarm states and emergency states of
input/outputs of the unit and information on set operation modes.