TYPE C
BALANCED FLUE SYSTEM, COMBUSTIVE AIR AND COMBUSTION PRODUCTS
TAKEN/THROWN FROM/TO THE OUTSIDE
- Before fixing the connection pieces it is necessary to remove the grilles at the exhaust outlet
and fresh air intake (1).
- After removing the grilles, replace them with connection pieces Ø100 (2) enabling so the
installation of the pipes with sealing ring (approved with the unit).
Type C12 appliances
Balanced flue heater
The distance between the 2 pipe ends must be at least 500 mm. The fresh air inlet must be
situated at a height of more than 1m from the floor or from any other wall.
The flue outlet should be located under the fresh air intake.
The maximum length of the pipes (supply and exhaust pipes) must not exceed:
-
Combustion products outlet: 4m straight 2 elbows of 90°.
-
Combustive air inlet: 4m straight 2 elbows of 90°.
(see also tabel at pag.13)
CAREFUL : refer to the rules in force.
N ° Designation
1
Combustion products outlet for insulated pipe Ø 100
2
Combustive air inlet for insulated pipe Ø 100
3
Non supplied insulated pipe Ø 100
4
Wall balanced flue terminal Ø 150 for two insulated pipes Ø 100
5
Outside wall of the building
6
Grid against birds
1
1
2
2