REPLACEMENT OF PARTS : 
 

Mono-electrode : 

Dismantle  the  electrode  carrier  by  unscrewing  fixation  screws.  Change  the  set  if 
necessary. The gap between the electrode and the earth electrode must be 4 mm. 

Burner and injector : 

Dismantle the electrode carrier. Unscrew the burner, unscrew the injector and change 
them if necessary. When the injector is dismantle, the joint must be replaced. 

Ignition and security box 

To  take  it  out,  unscrew  the  screw  on  the  cover,  unplug  the  connector  and  the  HT 
ignition connector. 

Pressure switch  

Open the superior bonnet, disconnect and identify the cable terminals and take out the 
pressure switch from it support. 

Fan Motor Group 

Loosen the 4 nuts to easily remove the fan motor group.. To unfix the turbines, loosen 
the six-sided nut by means of an Allen key on the flat surface of the motor axe.

 

 

13 Gas change

 

 
- The gas conversion must be done by qualified technicians. 
- When converting to another gas type, only the injector (5) must be changed. 
- We refer to the table at page 5 showing the injector diameters to be respected. 
-  This  table  also  indicates  the  inlet  pressure  and  the  pressure  by  injector  that  must  be 
respeced  
 

Note :

 A conversion kit is available on demand (consult our price list for components). The kit 

comprises :  injector, seal and gas label (must be adhered on the old label). 
 
Successive checks to be done 

 

-  Check  inlet  pressure  of  working  unit  by  means  of  a  manometer  connected  to the pressure 
connection (2) 

(See also table at page 5). 

- Check pressure at gas pressure connection (4). 
- Adjust pressure at the injector by using the adjustment screw. (3) 

(See table on page 5). 

- Fix appropriate gas label

 

 
Note : 

For  the  3rd  family  gases  3+  PROPANE  or  BUTANE  the  regulator  is  blocked  (3) 

(completely screwed in). 

 
 
 

Mark   Designation 

Electrovalve inlet 

Supply pressure intake (unblocked the screw 
in order to measure the pressure) 

Pressure regulator (remove the brass plug 
terminal in order to access to the regulator 
screw) 

Injector pressure intake (unblocked the 
screw in order to measure the pressure) 

Brass injector (carved in mmx100) 

 

Содержание BTwin BTH25

Страница 1: ...nt carefully before commencing the installation and leave it with the user after installation The document accompanying each unit is meant for the installer and the user This document contains instructions for installing the heater and flue system and describes in particular how to carry out gas connection electrical connection Subcontractors must also receive this document ...

Страница 2: ... 2 ...

Страница 3: ...g height 7 EVACUATION OF COMBUSTION PRODUCTS P 12 Type A Type B Type C 8 INSTALLATION METHOD CONNECTIONS P 17 a Electrical connection b Flue system c Gas connections d Option Failure signal transmission 9 TEMPERATURE REGULATION P 18 10 PROGRAMMING P 19 11 SETTING UP P 19 12 MAINTENANCE P 19 13 GAS CHANGE P 21 14 FAULTS POSSIBLE CAUSES SOLUTIONS P 22 15 ELECTRICAL SCHEMA P 23 16 OPTIONS ON REQUEST ...

Страница 4: ...e corrosive fumes even if there are small quantities of them whose combination with water vapour and or combustion products will entail abnormal deteriorations of the appliances For example chlorinated sulphurous ammonia or sodium products and diverse acid products All the requirements of the present regulation concerning ventilation and purifying shall be respected GUARANTEE LIMITS Warranty is vo...

Страница 5: ...gm diameter nihil Air pressure switch adjustment Pa 49 Turbine discharge mm Ø133 Weight kg 72 Adjustments in function of gaz Distributed gas 2H 2E 2L 2E 3P 3B Gas category for France II2Er3 x x x x Gas reference G20 G25 G31 G30 Heat input Hi of gas reference 1013mbar 10référence1013 mbar 15 C 34 02MJ m3 29 25MJ m3 46 34MJ kg 45 65MJ k g Nom Inlet pressure mbar 20 25 37 29 Min inlet pressure min mb...

Страница 6: ... 6 3 Dimensions Combustion air inlet opening Flue pipe outlet opening ...

Страница 7: ...b Appliance assembly The 2 long tubes A are identical with no special way of assembly Install the tubes in the fastening rings C fixed on the traverses B Pay attention to the direction of the traverses B Ensure that fixing holes are always in the bend direction Put the turbulators D inside the tubes Tube extractor side Provide each extremity with the 2m length turbulators D A A B B B C D D ...

Страница 8: ...t the moving burner block will come to a standstill Attention Take off the plastic protection of the reflectors G Put the fixing brackets of the reflectors H in open position Place the reflector G with the rectangular nick at the Ubend side into the brackets grooves Put the fixing brackets of the reflectors H in closed position by blocking the screw for maintaining the reflectors in place Inclinat...

Страница 9: ...tween pillars or against a wall Optional fixing parts can be supplied by GAZ INDUSTRIE ATTENTION For a good system efficiency do not incline the unit up to 30 Kit composition Model Horizontal hanging Wall hanging Reference of the kit Reference of the kit BTH25 0340131 0340119 HORIZONTAL HANGING WALL HANGING Burner side Extractor side F E G B A C 3 fixing holes Ø 11 ...

Страница 10: ...40mm 10 The total gradient of the heater must be 40 mm 10 in the direction of the Ubend Very important Make use of a flexible suspension system enabling the expansion of the emitter tubes but avoiding extreme oscillations Wall supports supplied on request by GAZ INDUSTRIE take this instruction into account Mark Designation A Required anchor points Wrong Wrong Good ...

Страница 11: ...ion PARTICULAR CASES 1 During the installation of an appliance above an overhead crane provide if necessary the protection of the crab s motor and of electrical equipments by the means of an insulating sheet 2 Avoid the installation of radiant tubes above bulky machines or stores which could prevent the diffusion of radiation towards the workers or users 3 In the presence of lifting ramps vehicle ...

Страница 12: ...ne which has been controlled for the CE mark However they can only be installed and used in well ventilated premises Radiant tubes can be installed without evacuation ducts for the combustion products within the limits of the regulations in force In that case no modification has to be brought to the units which are already equipped with a protection grille Attention In public buildings the evacuat...

Страница 13: ...eter can be accepted after the connection piece It must be made out of stainless steel or aluminium with smooth and rigid duct The evacuation must be realized according to the norms in force in each concerned country The maximum lenght of the exaust pipe do not be up than 8 meters 3 bends 90 1 terminal see on the spreadsheet herunder The duct must not include low point Any accessory made out of pl...

Страница 14: ...ection of this duct is made on the side of the main duct collector and not from below Place the dilution piece on the tube coming from the appliance and fix the 3 fixing parts by the means of screws or rivets Do not take off the screwed rod which is used as a thrust Plan for that the air entry in the building is a minimum of 10m3 h per kW Details for the connection on collector N Designation 1 Col...

Страница 15: ...esh air inlet must be situated at a height of more than 1m from the floor or from any other wall The flue outlet should be located under the fresh air intake The maximum length of the pipes supply and exhaust pipes must not exceed Combustion products outlet 4m straight length 2 elbows of 90 Combustive air inlet 4m straight length 2 elbows of 90 see also tabel at pag 13 CAREFUL refer to the rules i...

Страница 16: ... Combustion air inlet opening see table terminals 3 Piping Ø100 AC TR 100 4 Roof terminal Ø 150 for sealed pipes Ø 100 AC VT 100 5 Roof building 6 Sealing roof terminal not supplied 7 Grid against birds 8 Distance between centres 182 mm Reference tabel terminal kit BTH25 0340150 ...

Страница 17: ...ay on the converter or on the fonctional block of the appliance b Flue system F1 Flue outlet connection Ø100 accessory Gaz Industrie F2 Exhaust pipe Ø97 made of rigid material not supplied c Gas connection G0 Gas connection of the unit G gas male G1 Flexible pipe special model NF approved for public buildings Ensure pipe is not liable to pressure load possible to replaced with copper tube with min...

Страница 18: ...a homogeneous radiation To insulate the sensor from the wall on which it can be found in order to avoid the cold radiation of the wall through the interposition of an insulating material glass wool wood etc The connection between sensor and regulator must be made out of armoured cable or phone cable 2 pairs In any case do not put these wires in the cable path which already contains many wires carr...

Страница 19: ...ifferential pressure switch When the negative pressure is sufficient the ignition spark starts and the electromagnetic gas valve opens When the sensor detects the flame the ignition spark stops and the appliance functions as long as it is supplied in gas and in electricity If for whatever reason the flame is no longer detected the electro valve closes and the unit goes to lockout Then the applianc...

Страница 20: ... motor axis Remove dust with compressed air careful with the turbine over speed and clean the aeration ears 5 Ignition and security box Remove the electrical plate and remove dust if necessary Check that the control contact of negative pressure occurs correctly 6 Gas tray set and mono electrode Remove the electrode mounting panel disconnect the electric wires inspect the electrode brush it and cha...

Страница 21: ...gas type only the injector 5 must be changed We refer to the table at page 5 showing the injector diameters to be respected This table also indicates the inlet pressure and the pressure by injector that must be respeced Note A conversion kit is available on demand consult our price list for components The kit comprises injector seal and gas label must be adhered on the old label Successive checks ...

Страница 22: ...or changed Replace them correctly To be changed To be cleaned compressed air The pressure switch works correctly but there are no sparks Cracked electrode Too big gap for ignition electrode Faulty control box To be changed To be adjusted 3 mm 1 mm To be changed Sparks occur but the burner ignition does not occur Faulty electro valve Ignition and security box Electrode out of position Default of ga...

Страница 23: ...30V 2 Fuse 3 Yellow lamp Operating 4 Red lamp Defect 5 Motor supply 6 Pressure Switch 7 Earth of carter box 8 Earth of valve 9 24V connector 10 230V connector 11 Security and ignition box 12 Electro valve 13 Ignition and ionisation electrode 14 NTC Wiring ...

Страница 24: ...ts BTH25 2 Gas regulator Réf 10 21 215 4 Electric control box Réf 04 80 904 mono electrode assy Réf 10 30 016 1 Plug socket male and female Réf 02 80 217 3 Yellow inspection window Réf 10 25 243 3 Red inspection window Réf 10 25 244 5 Fan motor group BTH25 Réf 06 10 032 6 Pressostat BTH25 Réf 10 21 208 49 ...

Страница 25: ...exts Organisations which have the power to interfere before during and after the setting up of appliances have to be consulted before the installation of the appliance in order to be informed about the norms and rules in force ...

Страница 26: ... 26 ...

Страница 27: ... 27 ...

Страница 28: ... 28 ...

Отзывы: