3 – Installation & Wiring
T1 CrossConnect Installation & Operation Manual
Version 2
GatesAir
3-17
Intraplex Products
Table 3-14. Power and Alarm Connectors
Terminal
Description
DCS-9500 Pin
Equivalent
GND
screw
Chassis GROUND.
13
RING
GEN
RING GENERATOR input. For an external ring generator referenced to -48VDC
Signaling Battery input. Connect one side of the ring generator to this point, and
the other side to the SIG BAT input.
WARNING!
The ring generator must be externally fused or have its current
limited.
14
SIG BAT
-48VDC SIGNALING BATTERY input. For connection to an external signaling
voltage source when this is needed by one or more channel modules. This input
may also be connected to an external loop current generator.
WARNING!
This voltage source must be externally fused or its current limited.
15
+BAT R
Not used
None
-BAT R
Jumper this terminal to SIG BAT in a DC-powered shelf requiring talk battery.
None
+BAT
Battery common (+DC power input)
None
-BAT
Battery (-DC power input)
None
ALERT
NO
ALERT relay: normally OPEN contact*
3
ALERT
COM
ALERT relay: COMMON
11
ALERT
NC
ALERT relay: normally CLOSED contact*
4
ALARM
NO
ALARM relay: normally OPEN contact*
1
ALARM
COM
ALARM relay: COMMON
9
ALARM
NC
ALARM relay: normally CLOSED contact*
2
* When the shelf power is not on, all relays default to their alarm positions; normally open contacts
are closed and normally closed contacts are open.