www.gastron.com
30
_
31
GTC-200F
Instruction Manual
- Mode where the values converted in processor by inputting 20mA current in (mA) terminal are
displayed as figures.
- If "Func" key is pushed when the displayed figure is stable, the current input value is set and the next
item is entered into.
- When "Reset" key is pushed, the concentration display mode is returned to.
- Mode for setting output current of 4mA when "-Out" was selected the next mode for input current mode,
and the message is displayed as "A-04".
- If "Func" key is pushed when the ammeter accurately displays 4mA by pushing "▲" key or "▼" key
while watching the ammeter after connecting the ammeter to 4~20mA output terminal, the output
current value is set and the next item is entered into.
- When "Reset" key is pushed, the concentration display mode is returned to.
- Mode setting for 20mA output current with the message being displayed as "A-20".
- If "Func" is pushed when the ammeter accurately displays 20mA by pushing "▲" key or "▼" key while
watching the ammeter after connecting the ammeter to 4~20mA output terminal, the output current
value is set and the next item is entered into.
- When "Reset" key is pushed, the concentration display mode is returned to.
- The message informing completion of the setting function is displayed as "End" for 2 sec, and
the display state of gas concentration is returned to.
10.1. Basic configuration
[Figure 10. Outline drawing for basic product]
10. Outline drawing and Dimensions
9. How to operate Channel Unit