GTC-200A
6
3-3. Channel Unit
Channel Control Unit
1
Input type
4-20mA.DC / Full Scale
2
Measurement display
0.000 to 9999 Digital (settable by user)
3
Measurement
Accuracy
FND Digital
–bigger one between ±1% Full Scale or 1 Digit
LED Bar --- bigger one between ±1% Full Scale or 1 Digit
4
Input check interval
100 ms
5
Alarm setting
3 stage Alarm (settable by user)
6
Alarm setting display
3 Color Bar Graphic (Green/Red/Yellow LED)
7
Alarm display
LED Bar Graphic
8
Alarm reset
Manual (Common Unit)
9
Self diagnosis
Test Switch & Reset Switch
10 Control In/out
RS-485
11 Measurement Output
4-20mA.DC / Full Scale
12 Alarm Output
Fault Alarm - STDT Relay Dry contact Signal Output
Alarm 1 STDT Relay Dry contact Signal Output
Alarm 2 STDT Relay Dry contact Signal Output
Alarm 3 STDT Relay Dry contact Signal Output
* Relay Dry contact capacity : AC125V 10A
13 Operating Power
DC 24V
3-4. Wall Mount Type
Wall Mount Type
1
Input Power
AC 110V/220V 50/60Hz (default: AC220V 50/60Hz)
2
Applicable SMPS
capacity by
Channel quantities
Channel
Capacity
3(4) Channel
24V 1.5A (24V 1.5A)
5(6) Channel
24V 2.1A (24V 2.1A)
7(8) Channel
24V 2.1A (24V 3.5A)
9(10) Channel
24V 3.5A (24V 3.5A)
**( ): quantities and capacity when there is no Power Unit