GTC-200A
19
-. By pressing
“▲” or “▼”, decimal point can be changed in 3 types.
-.
Press “FUNC” key when desired decimal point is displayed to set the point
and go to next item
-.
If pressing “RESET” key, returns to density display mode.
-. High Scale (Maximum display value of gas density) is displayed as
“H-SL”
-.
Press “Func” key to go into High scale setting mode
-.
If pressing “RESET” key, returns to density display mode.
-. High Scale value was set when shipping from factory according to
domestic law
-.High Scale value can be changed according to measuring range with
“▲”
or
“▼”(increase or decrease).
-.If desired High scale value is displayed, press
“FUNC” key to set the value
as High Scale and go to next item.
-.
If pressing “RESET” key, returns to density display mode
-. This scale is set as same as detection range of gas detector at the factory.
Ex) when set Range as 100
4 mA.DC input ................... 0 Display
20 mA.DC input ................... 100 Display
-.SAD (compensating error from gas detector) setting message is displayed
as
“SAd ”.
-.
Press “Func” key to go into SAD value setting mode.
-.
If pressing “RESET” key, returns to density display mode
-.When pressing
“▲” or “▼” key, SAD value is increased or decreased (in
case of negative number,
“-“ sign is added and displayed.
-.If desired SAD value is displayed, press
“FUNC” key to set the value as
SAD and go to next item.
-.
If pressing “RESET” key, returns to density display mode
ex) In case of setting SAD as 2 : if output error from gas detector is -2, the
display will be -2. In this case, User should compensate 2 (SAD setting
value) to display 0 on FND.
-. Channel Number setting message (setting recognition number of each
channel unit) is displayed as
“CHno ”.
-.
Press “Func” key to go into Channel Number setting mode..
-.
If pressing “RESET” key, returns to density display mode
-.Common unit can check operation status of each channel unit with channel
number and this mode is to input each number (address) of channel unit.
When pressing
“▲” or “▼” key, address no. of channel unit will be
increased or decreased.
-.If desired address number is displayed, press
“FUNC” key to set the value
as Address NO. and go to next item (Alarm Reset Type function).
-.
If pressing “RESET” key, returns to density display mode
-. If Channel No. was not inputted, Channel Unit and Common Unit can
not communicate with each other.
-. Please make sure to assign different number to Channel units.
6-3-5. Alarm Data setting
-.
Push “Func” for over 2 seconds in gas density display mode and go into
alarm data setting mode.
-.(During alarm data setting mode, automatically return to density display