17m 16m 15m 14m 13m 12m 11m 10m 9m 8m 7m 6m 5m 4m 3m 2m 1m
3.0 -
mounTinG
1
1
2
2
3
3
For optimal detection coverage the Gassonic Surveyor should be
mounted at a height of 1 to 2 meters above potential leak spots, and
if possible in a position which makes it accessible for maintenance
purposes. In special cases, such as installation over compressors,
the height can be increased.
The Gassonic Surveyor can be mounted on a pole or a wall using the
optional mounting bracket UA1352A for standard horizontal mount-
ing or on the 45° mounting bracket UA1353. It can also be mounted
on a ceiling, on structural beams or similar non-vibrating structures.
As it primarily detects in a downward direction the unit must be
mounted with the microphone compartment facing down. This will
also prevent dirt from collecting in the wind screen, which may block
the sound.
To ensure optimal performance, correct mounting of the gassonic
surveyor is essential.
Mount the detector so it is clear of solid physical structures such as walls and heavy machinery, as these will dampen
any ultrasonic noise, leading to reduced detection coverage. Normal piping will not affect the coverage.
Full coVerage
reduced coVerage
obsTrucTion e.g. a concreTe wall
If necessary, the Gassonic Surveyor can be
mounted with an inclination not exceeding
45°. If mounted next to a wall, the inclination
will provide improved coverage. The optional
mounting bracket UA1353 can be used for
mounting at a 45° angle.
1m 2m 3m 4m 5m 6m 7m 8m 9m 10m 11m 12m 13m 14m 15m 16m
45˚
Installation and User Guide for Gassonic Surveyor (BB6019-01)
Page 5