Safe area
Hazardous area
V+
GND
I_SOURCE
REL1
REL2
Gassonic Surveyor
Specification for the sum of
Pin 1, 3, 4 and 5
in respect to Pin 2:
Ui: 28V dc
Ii: 220mA dc
Pi: 950mW
Ci: 14nF
Li: 10µH
Minimum specification:
Supply voltage: 9 V.
Supply power: 600, mW.
(350 mW. with Io= 0mA)
Barriers / Isolators
This could be a number of
different barriers or isolator.
(see example drawings)
NB: When choosing barriers
or isolators ensure that
safety description is fulfilled.
5
4
3
2
1
U
Max.
500
U_SUP
24VDC
24VDC
0V
IS Earth
0V
U
Min.
5K6
0V
Safety description:
NB: Values given to I.S. parameters are the total sum of
inputs.
When input voltage is 28 Vdc the current can not
exceed 120 mA, and when the input current is equal to
220 mA Vdc the voltage must not exceed 17,5 Vdc.
Installation in accordance with 60079-14 and -25 or correspond-
ing local regulations and laws.
Power supply:
U
i
= 28/17.3 Vdc
I
i
= 120/220 mAdc
P
i
= 950 mW
4-20mA source: output:
U
o
= Ui
I
o
= Ii
Relay output:
U
i
= 28/17.3 Vcd
I
i
= 120/220 mAdc
P
i
= 950 mW
Specific safety descriptions
Control room
Cabel param from En60079-14:
220 pF/meter
1 uH/meter or 30uH/ohm
Generic wiring diagram for Gassonic Surveyor. Connection data and example wiring diagrams of MTL and Peppel &
Fuchs barriers/isolators can be found in the Appendix. Any barriers/isolators can be used as long as their output safety
description does not exceed that of the Gassonic Surveyor. This product is designed to be installed according to IEC
Standard EN 60079-14.
Wire connectors on the unit are
individually marked for correct
wiring and reference.
14.0 -
WiRinG
Installation and User Guide for Gassonic Surveyor (BB6019-01)