4.2.6
AUTOMATIC AIR RELIEF VALVE
Wallcon X-treme boilers have an automatic relief
valve for the evacuation of the air accumulated in
the heat exchanger. However, for the evacuation of
the air that may occur in the installation, it is
necessary to place one or more automatic air relief
valves in the appropriate places of the installation.
Local regulations must be followed in this regard.
4.2.7
DEPOSIT AND DIRT SEPERATOR
To remove the dirt and particles form the water, a
strainer or deposit nd dirt seperator must be placed
on the return line of the boiler.
When the dirt, particles and similar deposits in the
system water are not cleaned;
The efficiency of the system decreases,
Installation equipments (pumps, valves, plate
heat exchanger, etc.) may be damaged due to
overheating
A boiler damage may occur due to heat
exchanger clogging. Manufacturer cannot be
held liable for damages that may occur in such
cases.
Strainers or deposit and dirt sepertors on the
system should be checked frequently and
cleaned if necessary.
4.2.8
AIR INLET FILTER (OPTIONAL)
If Wallcon X-treme boilers will be used in to a dirty
air environment, they must be supported with the
air inlet filters. This optional filter must be checked
regularly.
When the air inlet filter becomes dirty;
Emission values would be deteriorated and
efficient combustion wouldn’t be achieved.
The accumulation of soot occurs in the heat
exchanger.
Loud ignition and combustion occurs.
Overheating, leakage and deformation would be
observed in the flue system.
18
WALLCON X-treme 115-125-150
Manufacturer cannot be held liable for
damages caused by dirty combustion air.
Don’t block the air filter partially or totally.