Set the calibration point
Make sure the detector is connected correctly, power on until the
output of the detector is stable.
1. Press the "MENU" key on the remote controller, the detectorr
displays F-01.
2. Press the "+" key or the "-" key to adjust to F-07.
3.
Press the "OK" key to enter the gas concentration value display interface. The value can be
modified by the "+" and "-" keys to make the value consistent with the calibration gas concentration .
Press the "OK" key to display "PASS" briefly.
IR AL AH
IR AL AH
IR AL AH
IR AL AH
IR AL AH
IR AL AH
2.
Press the "+" key to display F-08,
●
Span calibration
1.
Press the "BACK" key to exit, the detector will display F-07.
IR AL AH
3.
Press the "OK" key again to enter the function interface. After adjusting the "0" displayed on the
interface to “1 " by the "+" key, press the "OK" key again to display the current detection reading.
IR AL AH
12