MDE-4319A TopKAT Fuel Managment System Installation Manual · November 2005
Page 7
General Installation
3 – General Installation
Rules for Proper Installation
1
Please read this entire manual before starting installation.
2
Internationally and domestically: All wiring is to be installed and used in accordance with all
applicable national, state, and local building/fire/electrical codes. Additionally, in the USA,
installations must comply with the National Electrical Code (NFPA 70), NFPA 30, and the
Automotive and Marine Service Station Code (NFPA 30A) codes and regulations. Canadian
installations must comply with the Canadian Electrical Code.
3
All wiring must be in threaded, rigid, metal conduit to provide the necessary shielding. DO
NOT use PVC conduit.
4
High-voltage (AC) and low-voltage (DC) must not be combined in a common conduit,
junction box, or wire trough unless cable is used as specified in
.
5
Power for the TopKAT (when used with mechanical interface), data terminal, and external
modem must come from a separate, dedicated, circuit breaker.
6
The TopKAT and peripheral equipment must be properly grounded.
7
Use terminal connectors on stranded wire.
8
Test pumps in the manual override position prior to system start-up.
9
DO NOT turn on the system power switch located in the head assembly. Power will be
applied to the system by the person performing the system start-up. Turning on this switch
prematurely may result in damage to the system and may void your warranty!
10
Check through all boxes and cartons before disposing of them for manuals, cables, connectors,
etc.
To reduce the risk of electrical shock when servicing, turn off all power to the pump/remote
dispenser. In submersible pump applications, turn off all power to the submersible pump
and any other remote dispensers which use that submersible pump. AC power can feed
back into a shut-off remote dispenser when dispensers share a common submersible pump
or starter relay.
WARNING
!
Pour réduire le risque de choc électrique lors de l'entretien/révision, coupez totalement le
courant à la pompe/distributeur éloigné. Dans les applications de pompe immersible, coupez
totalement le courant à la pompe immersible et tous autres distributeurs éloigné qui utilisent la
pompe immersible. Le courant alternatif peut alimenter de nouveau un distributeur éloigné à
l'arrêt quand les distributeurs partagent une pompe immersible commune ou un relais de
démarrage.