MDE-4319A TopKAT Fuel Managment System Installation Manual · November 2005
Page 93
Wiring Diagrams: Pulsers, Pumps, Dispensers
Mechanical PCU Option
Pulser Wiring Notes
1
All pulsers above are shown connected to hose 1.
2
Jumpers on the Pump Control PCB must be properly jumpered according to the pulser type.
This should be done by the person performing the start-up. Power to the system must not be
turned on prior to this set-up.
3
See
“Conduit Layout/Installation Specifications” on page 14
for detailed system installation
specifications.
4
When installed in a separate DC conduit, 18 AWG wires are required for installation.
Although it is recommended that DC pulser wires be run in a conduit separate from AC wires,
they can be combined in the same conduit with AC wires providing UL-Listed cable with the
following specifications is used:
• Conductor: 18 AWG stranded wire. Number of conductors to be determined by pulser
• Shield: Foil-wrapped 100% coverage and/or tinned copper braid 90% coverage
• Drain Wire: Stranded, tinned copper, 20 AWG or larger/or braided shield
• Voltage Rating: Maximum operating voltage of 600V
• Environmental: Gas- and oil-resistant; suitable for wet or dry locations.
Gasboy can supply Belden 1063A (P/N C09655) which is a UL-Listed, 4-conductor cable that
meets the requirements listed above.
Note: Belden 1063A is UL-Listed but not CSA listed.